ELE05-02037
| ELE-Aging Inspection | 11/15/2005 | 11/15/2005 | 11/15/2005 3:26:36 PM | | PART |
|
|
called contractor WSUC
|
ELE05-04147
| Temporary Service | 11/15/2005 | 11/15/2005 | 11/15/2005 2:28:52 PM | P | PASS |
|
|
ron ###-#### t/s u/g new ok
|
ELE05-03700
| Final | 11/15/2005 | 11/15/2005 | 11/15/2005 1:52:29 PM | P | PASS |
|
|
me; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok
|
ELE05-03700
| Final | 11/15/2005 | 11/15/2005 | 11/15/2005 1:51:54 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/15/2005 at 8:23:03 AM. Contact: ###-####.
|
ELE05-04145
| Permanent Service | 11/15/2005 | 11/15/2005 | 11/15/2005 12:51:31 PM | P | PASS |
|
|
###-#### - darrel p/s o/h rec. ok
|
ELE03-00484
| Final | 11/15/2005 | 11/15/2005 | 11/15/2005 12:02:33 PM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/15/2005 at 6:38:16 AM. Contact: ###-####. cor. fee due posted called 110.3(A) shall use manufactures listed equip grd kit per instructions, replace cut and damaged neutral bus,110.14 shall use splicing devices identified for cu/al, 250.8 shall not use SMS for grds or bonds, 680.26 bond all metal with 5 ft of spa to spa equip, seal unused openings
|
ELE05-04122
| Rough-In Permanent Service | 11/14/2005 | 11/15/2005 | 11/15/2005 10:48:35 AM | A | FAIL |
|
|
ron ###-#### cor. called 300.4(A)(1)&(D) nail plates adn 11/4"
|
ELE05-04128
| Final | 11/14/2005 | 11/15/2005 | 11/15/2005 9:52:33 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer cor. called 210.8(B) recept in bathrm needs gfci, 300.11(A) &314.23(D)(2) ceiling box needs support wires
|
ELE05-04130
| Final | 11/14/2005 | 11/15/2005 | 11/15/2005 9:22:38 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok
|
ELE05-04134
| Temporary Service | 11/14/2005 | 11/15/2005 | 11/15/2005 8:59:14 AM | A | FAIL |
|
|
Contact is Jeff.; Phone #: ###-#### Internet Inspection Request from: David Bonner cor. called 110.12 seal KOs, 110.3 & 300.10 needs bond bushings where RE washers are used, connector in myers hub cross threaded, 250.90,92 needs listed myers hub for service bonding requirements, 590.6(B) all recepts 240 volt need gfci protection
|
ELE05-02596
| Final | 11/14/2005 | 11/15/2005 | 11/15/2005 8:17:55 AM | A | PASS |
|
|
warren ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
|
ELE05-01286
| Final | 11/15/2005 | 11/15/2005 | 11/15/2005 12:00:00 AM | P | PASS |
|
|
wall signs ok
|