Inspections for the day of: Tuesday, November 15, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02037 ELE-Aging Inspection11/15/200511/15/200511/15/2005 3:26:36 PM PART
called contractor WSUC
ELE05-04147 Temporary Service11/15/200511/15/200511/15/2005 2:28:52 PMPPASS
ron ###-#### t/s u/g new ok
ELE05-03700 Final11/15/200511/15/200511/15/2005 1:52:29 PMPPASS
me; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok
ELE05-03700 Final11/15/200511/15/200511/15/2005 1:51:54 PMPPASS
Scheduled by a contractor via Hello! on 11/15/2005 at 8:23:03 AM. Contact: ###-####.
ELE05-04145 Permanent Service11/15/200511/15/200511/15/2005 12:51:31 PMPPASS
###-#### - darrel p/s o/h rec. ok
ELE03-00484 Final11/15/200511/15/200511/15/2005 12:02:33 PMAFAIL
Scheduled by a contractor via Hello! on 11/15/2005 at 6:38:16 AM. Contact: ###-####. cor. fee due posted called 110.3(A) shall use manufactures listed equip grd kit per instructions, replace cut and damaged neutral bus,110.14 shall use splicing devices identified for cu/al, 250.8 shall not use SMS for grds or bonds, 680.26 bond all metal with 5 ft of spa to spa equip, seal unused openings
ELE05-04122 Rough-In Permanent Service11/14/200511/15/200511/15/2005 10:48:35 AMAFAIL
ron ###-#### cor. called 300.4(A)(1)&(D) nail plates adn 11/4"
ELE05-04128 Final11/14/200511/15/200511/15/2005 9:52:33 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dana Moyer cor. called 210.8(B) recept in bathrm needs gfci, 300.11(A) &314.23(D)(2) ceiling box needs support wires
ELE05-04130 Final11/14/200511/15/200511/15/2005 9:22:38 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok
ELE05-04134 Temporary Service11/14/200511/15/200511/15/2005 8:59:14 AMAFAIL
Contact is Jeff.; Phone #: ###-#### Internet Inspection Request from: David Bonner cor. called 110.12 seal KOs, 110.3 & 300.10 needs bond bushings where RE washers are used, connector in myers hub cross threaded, 250.90,92 needs listed myers hub for service bonding requirements, 590.6(B) all recepts 240 volt need gfci protection
ELE05-02596 Final11/14/200511/15/200511/15/2005 8:17:55 AMAPASS
warren ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
ELE05-01286 Final11/15/200511/15/200511/15/2005 12:00:00 AMPPASS
wall signs ok