ELE05-03702
| Electrical Rough-In | 11/15/2005 | 11/15/2005 | 11/15/2005 4:24:54 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/15/2005 at 7:37:12 AM. Contact: ###-####. ok to cover ceiling
|
ELE05-03659
| Rough-In Permanent Service | 11/14/2005 | 11/15/2005 | 11/15/2005 3:21:58 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/14/2005 at 12:52:46 PM. Contact: ###-####. ric ok, p/s u/g n ok
|
ELE05-03278
| Electrical Rough-In | 11/15/2005 | 11/15/2005 | 11/15/2005 1:48:51 PM | P | PASS |
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles soffits and recessed lighting ok to cover, ceiling ok to cover
|
ELE05-04032
| Rough-In Permanent Service | 11/14/2005 | 11/15/2005 | 11/15/2005 10:37:58 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called cont, left corr notice,312.5 conductors shall be protected from abrasion, 800.133(A)(1) class 2 conductors shall not be run with class 1 ,300.4(A)&(D) 1 1/4" shall be maintained from edge of structural member,314.20 box shall be flush with combustible wall, BCC job id sticker shall be posted
|
ELE05-04112
| Rough-In Permanent Service | 11/14/2005 | 11/15/2005 | 11/15/2005 10:24:31 AM | A | PASS |
|
|
brian ; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, ric ok, p/s u/g n ok
|
ELE05-02783
| Electrical Rough-In | 11/14/2005 | 11/15/2005 | 11/15/2005 10:12:57 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 11/14/2005 at 4:59:52 PM. Contact: ###-####. see p/s
|
ELE05-04120
| Permanent Service | 11/15/2005 | 11/15/2005 | 11/15/2005 9:16:02 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack p/s u/g n ok
|
ELE05-03249
| Final | 11/14/2005 | 11/15/2005 | 11/15/2005 9:09:19 AM | A | PASS |
|
|
gene; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
ELE05-03620
| Rough-In Permanent Service | 11/14/2005 | 11/15/2005 | 11/15/2005 8:44:21 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla corr made, ric ok, p/s u/g n ok
|
ELE05-03664
| Final | 11/14/2005 | 11/15/2005 | 11/15/2005 8:11:03 AM | A | PASS |
|
|
Charlie; Phone #: ###-#### Internet Inspection Request from: Melyne Davis called contr for 1 recpt rev polarity, ok to final
|
ELE05-03847
| Final | 11/15/2005 | 11/15/2005 | 11/15/2005 7:10:58 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Clyde Logan Inspection cancelled from web by: Clyde Logan
|
ELE05-02783
| Permanent Service | 11/15/2005 | 11/15/2005 | 11/15/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/14/2005 at 4:59:52 PM. Contact: ###-####. corr made, p/s exst u/g, re-connect ok
|