Inspections for the day of: Thursday, November 15, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03400 Electrical Rough-In11/14/200711/15/200711/15/2007 4:52:57 PMPFAIL
jack - floor heat Phone #: ###-#### called corr., do not cover posted 110.3(B) floor heat not installed per manufactures instruction
ELE07-03130 Electrical Rough-In11/15/200711/15/200711/15/2007 3:49:38 PMPFAIL
casey Phone #: ###-#### all violations not corrected 250.148 grd all metal boxes, 300.4(D), 11/4" cables parallel, also jbox ceiling laundry rm shall be accessible, 334.23 protect cables within 6ft attic access, energy code shall use air tight cans
ELE07-03273 Final11/15/200711/15/200711/15/2007 3:14:50 PMPPART
please final the lobby, this seems to be going in phases. Phone #: ###-#### Internet Inspection Request from: Sean Peltier t/o looby anop
ELE07-03812 Electrical Rough-In11/14/200711/15/200711/15/2007 2:31:34 PMPPART
Homeowner will be home in the afternoon. Any questions or concerns please call Clay at ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan r/i ok called left message , no violations retained owner wired hot tub, no permit for it told owner she will have to secure electrical contr to secure permit for it also p/s calcs
ELE07-03440 Electrical Rough-In11/15/200711/15/200711/15/2007 1:36:39 PMPPART
conference and concrete encased electrode ok
ELE07-03811 Temporary Service11/15/200711/15/200711/15/2007 1:00:36 PMPPASS
Thank You!!
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s u/g new ok
ELE07-03810 Temporary Service11/15/200711/15/200711/15/2007 1:00:16 PMPPASS
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson
t/s u/g new ok
ELE07-03831 Electrical Rough-In11/14/200711/15/200711/15/2007 11:06:33 AMAPART
UNDERGROUND INSPECTION PLEASE @ WHEAT MONTANA BAKERY & DELI Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok
ELE07-03830 Rough-In Permanent Service11/14/200711/15/200711/15/2007 10:50:50 AMACANC
Ufer inspection. Phone #: ###-#### Internet Inspection Request from: Kathy Smith no p/s see added r/i
ELE07-03830 Electrical Rough-In11/15/200711/15/200711/15/2007 10:48:16 AMAPART
Ufer inspection. Phone #: ###-#### Internet Inspection Request from: Kathy Smith
electrodes ok
ELE07-03819 Electrical Rough-In11/14/200711/15/200711/15/2007 10:33:36 AMAPART
Phone #: ###-#### Internet Inspection Request from: Dan Rohl r/i garage and u/g ok needs lights for all exit doors, and address 250.32 for service at garage , note feeder art 225
ELE07-03727 Temporary Service11/15/200711/15/200711/15/2007 9:44:24 AMAPART
Scheduled by a contractor via Hello! on 11/15/2007 at 6:46:38 AM. Contact: ###-####. still needs to wire job trailer no final, t/s u/g new ok
ELE07-03662 Final11/14/200711/15/200711/15/2007 9:09:43 AMAPART
robert Phone #: ###-#### needs gfci garage recepts, and enclosure for phase converter
ELE07-03626 Final11/14/200711/15/200711/15/2007 8:36:50 AMAFAIL
Electrician is Fabian Luna. Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer see added p/s , corr outlet shall be tween 10ft 20ft, bond emt within 5ft, outside fixtures for sheds
ELE07-03626 Permanent Service11/15/200711/15/200711/15/2007 8:33:34 AMAPASS
Electrician is Fabian Luna. Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer p/s u/g rec. ok
ELE07-03626 Final11/13/200711/15/200711/14/2007 4:33:27 PMPCANC
electrician is Fabian Luna, inspection as late in the day as possible Phone #: ###-#### Internet Inspection Request from: Jim Burnette Inspection cancelled from web by: Jarrod Clymer