Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00620 INSP-Alarm Testing11/13/200711/15/200711/16/2007 2:08:44 PMAPART
See as-built plans marked for areas inspected today and noted items in need of revision including door release, adding SD at an electrical room, relocating three SD at the gas bunker, will review approved plans at the next scheduled visit.
BLD07-02477 FIRE-Final Inspection11/14/200711/15/200711/16/2007 7:54:27 AMPFAIL
Missing PFE, EM lighting, need to provide approved door hardware, see c/n completed per K. Roule.
BLD07-01746 FIRE-Final Inspection11/14/200711/15/200711/15/2007 4:25:55 PMAPASS
Fire life safety inspection passed.
FIR07-00590 INSP-Final Inspection11/14/200711/15/200711/15/2007 4:25:14 PMAPASS
Fire sprinkler permit finaled.
BLD07-00798 FIRE-Final Inspection11/14/200711/15/200711/15/2007 4:24:41 PMAPASS
Fire life safety finaled.
FIR07-00304 INSP-Final Inspection11/14/200711/15/200711/15/2007 4:16:45 PMAPASS
Corrections verified for completion, fire sprinkler permit finaled.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro11/14/200711/15/200711/15/2007 2:26:08 PMAPART
Rough-in is okay as noted on approved plans for the 4th floor NW quad. OH hydrostatic testing for this area also passed, also inspected overhead install at the 3rd floor west and south skybridges.
FIR07-00835 INSP-Sprinkler Rough-in11/15/200711/15/200711/15/2007 2:17:05 PMPPART
UG fire supply line is approved for cover, need to provide method for seismic clearance at the floor slab.
BLD07-01981 FIRE-Final Inspection11/14/200711/15/200711/15/2007 11:56:22 AMAFAIL
Missing the required fire extinguisher, manual flush bolts at the inactive door leaf at the main entry/exit are not allowed.
FIR07-00840 INSP-Final Inspection11/14/200711/15/200711/15/2007 11:54:14 AMAPASS
Fire alarm system modifications passed inspection, permit finaled.
FIR07-00796 INSP-Final Inspection11/14/200711/15/200711/15/2007 10:57:55 AMAPASS
Fire sprinkler permit finaled.
FIR07-00872 INSP-Final Inspection11/14/200711/15/200711/15/2007 10:57:05 AMAPASS
Hood suppression system functioned properly under test conditions, air balance report to be provided to today as agreed and prior to mech. permit final.
FIR07-00888 INSP-Sprinkler Rough-in11/14/200711/15/200711/15/2007 10:54:54 AMAPART
OH rough-in inspection passed.
FIR07-00464 FIR-Aging Inspection11/15/200711/15/200711/15/2007 8:14:41 AM DEFR
Work in progress.