Inspections for the day of: Tuesday, November 15, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02059 FIRE-Conference11/14/201111/15/20111/24/2012 12:11:31 PMADONE
Regarding coverage at the ATM room.
FIR11-00504 INSP-Final Inspection11/14/201111/15/201111/16/2011 4:47:33 PMPPASS
FIR11-00538 INSP-Final Inspection11/14/201111/15/201111/16/2011 4:47:09 PMPPASS
FIR11-00301 INSP-Sprinkler Rough-in11/14/201111/15/201111/15/2011 3:14:00 PMAPART
UG fire supply line and remote FDC piping at the SE corner okayed to bury. Note: contractor has utilized a restrained joint system per NFPA 13 10.8.3 in place of thrust blocking. Discussed bury depth requirements with contractor per civil drawing elevations- UG pipe to be maintained 4'6" below grade min.
FIR11-00534 INSP-Supply line flush11/11/201111/15/201111/15/2011 3:02:46 PMPPART
UG fire supply line flush completed acceptable.
FIR10-00524 INSP-Final Inspection11/15/201111/15/201111/15/2011 3:01:43 PMPPASS
Inspection passed. Fire alarm permit finaled.
FIR11-00528 INSP-Final Inspection11/14/201111/15/201111/15/2011 3:00:21 PMAFAIL
See plan annotations for noted items including notification appliance coverage and location issues, missing SD at the three liebert units, batteries at the FACP, etc.
FIR11-00397 INSP-Final Inspection11/14/201111/15/201111/15/2011 10:32:12 AMADEFR
Don Phone #: ###-####
BLD10-02929 FIRE-Final Inspection11/14/201111/15/201111/15/2011 10:31:09 AMAPASS
Correction items verified for completion. Signature card not available at the time of inspection. Life safety finaled.