Inspections for the day of: Tuesday, November 15, 2011.
Number of inspections: 9
Percentage of inspections complete: 89 %
Percentage of inspections not complete: 11 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02336 FIRE-Final Inspection11/15/201111/15/201111/15/2011 3:13:53 PMPPASS
life safety passed
FIR11-00570 INSP-Final Inspection11/15/201111/15/201111/15/2011 2:56:04 PMPPASS
permit finaled
BLD11-01527 FIRE-Final Inspection11/15/201111/15/201111/15/2011 2:28:15 PMAFAIL
Need the insulation that is blocking the upright sprinkler heads repaired and the overspaced sprinklers and pendant sprinklers with no ceilings addressed.
BLD11-02634 FIRE-Final Inspection11/14/201111/15/201111/15/2011 2:18:07 PMAFAIL
See the upper level and lower level approved floor plans for a list of corrections that need addressed. They include modified sprinkler coverage missing exit signs and missing occupant load sign.
FIR11-00579 INSP-Sprinkler Rough-in11/14/201111/15/201111/15/2011 11:54:43 AMAPASS
First and second floor hard lid areas are ok to cover. I noted that the sprinkler protection provided over the main entry canopy has not been installed. Mike is going to have his office contact me on this.
FIR11-00544 INSP-Sprinkler Rough-in/Hydro11/14/201111/15/201111/15/2011 11:11:41 AMAPASS
Rough-in passed. One pendant needs to be relocated in the Laundry room and as-builts showing the revised pipe routing are needed. The tenting still needs to be done.
BLD11-02211 FIRE-Final Inspection11/14/201111/15/201111/15/2011 11:04:40 AMAFAIL
Provide emergency lighting in the break room as per the plans.
BLD11-00389 FIRE-Final Inspection11/15/201111/15/201111/15/2011 10:23:35 AMPPASS
life safety passed
BLD11-02165 FIRE-Conference11/15/201111/15/2011 P