Inspections for the day of: Thursday, November 15, 2012.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-01915 FIRE-Conference11/15/201211/15/201211/15/2012 3:37:35 PMPDONE
Warren, the electrician, contacted me wanting to know if exit discharge lighting is required. I found that per the building inspectors review notes the exit discharge lights are required.
BLD12-02323 FIRE-Conference11/15/201211/15/201211/15/2012 2:51:41 PMPDONE
Per Boise Fire Dept. request I left correction notice requiring the existing FDC at the east wall to meet NFPA 13 requirements for height above access level (18" to 4'). Contractor stated that it will be no problem since a new docking is going to be constructed under it.
FIR12-00513 INSP-Final Inspection11/15/201211/15/201211/15/2012 2:43:28 PMPPASS
permit finaled
FIR12-00033 INSP-Alarm Testing11/14/201211/15/201211/15/2012 11:35:55 AMAPASS
The testing of audio/visuals for the 1st floor lobby and misc. offices at the west side of building passed. One strobe in the office had to have the candella increased due to being overspaced and one smoke detector in the lobby was located too close to a supply diffuser. The diffuser was relocated. EOL voltage stayed above 19.6 volts on the two associated notification circuits tested. I also noted that the smoke detector in the main entry, where the FACP is located, is located too close to a supply diffuser and will need to be relocated prior to testing of that area. The manual pull station at the main lobby exit doors is located on the opposite side of the bank of doors from what is shown on the approved drawings.
FIR12-00549 INSP-Alarm Testing11/13/201211/15/201211/14/2012 3:24:37 PMACANC
We need to schedule a fire alarm test for the 1st main lobby and misc. offices at Boise city hall, we need to start at 7am. please call mike to confirm ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
BLD12-02043 FIRE-Final Inspection11/14/201211/15/201211/14/2012 2:14:15 PMAPASS
life safety passed