ELE13-03160
| Electrical Rough-In | 11/13/2013 | 11/15/2013 | 11/15/2013 4:41:09 PM | A | NH |
|
|
Phone #: ###-#### >> Inspection requested via web by Mark M Unable to meet up with general foreman due to scheduling conflicts.
|
ELE13-03137
| Electrical Rough-In | 11/14/2013 | 11/15/2013 | 11/15/2013 4:35:52 PM | P | PASS |
|
|
>> Inspection requested via web by Terry Scott garage and rooms over garage rough in ok cover
|
ELE13-03101
| Final | 11/14/2013 | 11/15/2013 | 11/15/2013 4:10:06 PM | P | FAIL |
|
|
If no one is there the lockbox is 6360, please let me know if there are any issues. Thank You. Clay Phone #: ###-#### >> Inspection requested via web by Clay Morgan 210.62-Showroom receptical outlet ahall be installed with in 18" of window
|
ELE13-02057
| Electrical Rough-In | 11/15/2013 | 11/15/2013 | 11/15/2013 3:53:55 PM | P | PASS |
|
|
Robert. 6th floor wall cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy 6th floor wall rough in ok cover
|
ELE13-02788
| Final | 11/14/2013 | 11/15/2013 | 11/15/2013 3:26:47 PM | P | CANC |
|
|
Contact: Josh Mangum Phone #: ###-#### >> Inspection requested via web by Deb Gooden Rescheduled to monday the 18th
|
ELE13-03100
| Final | 11/15/2013 | 11/15/2013 | 11/15/2013 3:21:09 PM | P | FAIL |
|
|
please call so I can let you into the home Phone #: ###-#### >> Inspection requested via web by Eddy Udry 110.26- A flat platform 30" wide and 36" deep shall be provided in front of service for work space.
|
ELE13-03100
| Permanent Service | 11/15/2013 | 11/15/2013 | 11/15/2013 3:10:54 PM | P | PASS |
|
|
please call so I can let you into the home Phone #: ###-#### >> Inspection requested via web by Eddy Udry p/s o/h rec ok
|
ELE13-02449
| Electrical Rough-In | 11/15/2013 | 11/15/2013 | 11/15/2013 1:45:15 PM | P | PASS |
|
|
Potting for light inspection please_Mike Phone #: ###-#### UL listing confirmed. Rough in ok cover
|
ELE13-03004
| Electrical Rough-In | 11/15/2013 | 11/15/2013 | 11/15/2013 1:11:42 PM | P | PASS |
|
|
floor heat insp// Dennis (homeowner call for acces) -- (Mike, contractor ###-####) Phone #: ###-#### Floor heat rough in ok cover
|
ELE13-03197
| Electrical Rough-In | 11/14/2013 | 11/15/2013 | 11/15/2013 12:47:23 PM | A | PASS |
|
|
Tricky to find, call for info. Thanks Richard Phone #: ###-#### >> Inspection requested via web by Richard Floor heat home runs in floor rough in ok cover
|
ELE13-01478
| Final | 11/15/2013 | 11/15/2013 | 11/15/2013 12:19:13 PM | A | PASS |
|
|
please call before arriving. I need to make sure homeowner is there to let you in. Thank You Phone #: ###-#### >> Inspection requested via web by Eric Brown Final ok
|
ELE12-01710
| Permanent Service | 11/14/2013 | 11/15/2013 | 11/15/2013 10:59:31 AM | A | PART |
|
|
Contact: Wes Powell Phone #: ###-#### >> Inspection requested via web by Deb Gooden Fire pump, and generator rough in ok
|
ELE13-03195
| Electrical Rough-In | 11/14/2013 | 11/15/2013 | 11/15/2013 9:16:04 AM | A | PASS |
|
|
Master bath remodel Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot Rough in ok cover
|
ELE13-01051
| Electrical Rough-In | 11/14/2013 | 11/15/2013 | 11/15/2013 8:52:45 AM | A | PASS |
|
|
Bruce Phone #: ###-#### Service rough in ok
|
ELE13-01051
| Permanent Service | 11/15/2013 | 11/15/2013 | 11/15/2013 8:52:18 AM | P | PASS |
|
|
Bruce Phone #: ###-#### p/s o/h n ok
|
ELE13-03191
| Electrical Rough-In | 11/14/2013 | 11/15/2013 | 11/15/2013 8:45:11 AM | A | PASS |
|
|
rough in for cover on the new framed walls Phone #: ###-#### >> Inspection requested via web by Brad Baker Wall rough in ok cover
|
ELE13-02983
| Electrical Rough-In | 11/14/2013 | 11/15/2013 | 11/14/2013 3:26:44 PM | A | PASS |
|
|
michael - floor heat inspection Phone #: ###-#### rough in ok cover
|