Inspections for the day of: Friday, November 15, 2013.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-03024 Temporary Service11/15/201311/15/201311/18/2013 8:56:29 AMPPASS
HP. Temp service. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy t/s o/h n ok
ELE13-03042 Electrical Rough-In11/15/201311/15/201311/15/2013 4:26:55 PMPPASS
bonding // Roger Phone #: ###-#### rough-in ok cover trench and pool bonding back to back wall of shed
ELE12-00814 ELE-Aging Inspection11/15/201311/15/201311/15/2013 3:55:42 PM DONE
contractot said he would schedule a final inspection next week 11/18/13 thu 11/23/13
ELE12-00002 ELE-Aging Inspection11/15/201311/15/201311/15/2013 3:42:01 PM DONE
contractor will complete service panel directory and call for final
ELE13-03202 Final11/15/201311/15/201311/15/2013 3:13:20 PMPNH
storage gate code is 4757 compound gate to cell site is 1270 Phone #: ###-#### >> Inspection requested via web by ben wolf No access, No job identifcation tag. Compond gate paddle locked. no answer from contact person. call back in for rough-in inspection.
ELE13-03187 Electrical Rough-In11/15/201311/15/201311/15/2013 2:44:57 PMPPASS
Underground inspection Phone #: ###-#### >> Inspection requested via web by Chris Chesnut correction done, rough-in ok cover underground
ELE13-03189 Final11/15/201311/15/201311/15/2013 2:27:34 PMPFAIL
GFI has been installed Phone #: ###-#### >> Inspection requested via web by Brad Baker MC cable hanging though t-grid ceiling with open handy box in area of work being performed, no other electrical permits?
ELE13-03180 Electrical Rough-In11/14/201311/15/201311/15/2013 2:02:27 PMPPASS
underground Phone #: ###-#### >> Inspection requested via web by Louis Keller rough-in ok cover new underground conduits to existing pool.
ELE13-03025 Temporary Service11/15/201311/15/201311/15/2013 1:08:59 PMPFAIL
HP. Temp service. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Ground rod cut-off NEC Grounding electrode shall be at least 8ft. in contact with the soil.
ELE13-03067 Electrical Rough-In11/14/201311/15/201311/15/2013 12:40:32 PMAPASS
r/i on bathrooms -- Daniel Phone #: ###-#### rough-in ok cover bathrooms only
ELE13-03188 Final11/15/201311/15/201311/15/2013 12:39:21 PMPPASS
GFI protection has been installed Phone #: ###-#### >> Inspection requested via web by Brad Baker correction done, final ok
ELE13-02595 Final11/14/201311/15/201311/15/2013 12:08:13 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Jay Symonds final ok
ELE13-03187 Electrical Rough-In11/14/201311/15/201311/15/2013 9:13:28 AMAFAIL
Underground Inspection Phone #: ###-#### >> Inspection requested via web by Chris Chesnut NEC 517.18 Floor boxes in patient care require redunit grounding, metal raceway
ELE13-01824 Final11/14/201311/15/201311/15/2013 8:44:32 AMAPASS
garage code 0243 Phone #: ###-#### >> Inspection requested via web by Heath Thomas final ok
ELE13-02427 Final11/14/201311/15/201311/15/2013 8:41:59 AMAPASS
Key is on top of meter in back yard no one is living there Phone #: ###-#### >> Inspection requested via web by Jay Symonds final ok
ELE13-03017 Final11/12/201311/15/201311/15/2013 8:24:23 AMAPASS
Gena-Before 8:30 please Phone #: ###-#### final ok
ELE13-03017 Electrical Rough-In11/15/201311/15/201311/15/2013 8:23:58 AMAPASS
Gena-Before 8:30 please Phone #: ###-#### ETL listed equipment rough-in ok
ELE13-03196 Final11/14/201311/15/201311/15/2013 8:10:48 AMACANC
Contact: Marty Vanness... Late morning if possible please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
ELE13-01797 Electrical Rough-In11/14/201311/15/201311/14/2013 2:42:09 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Debby Ellis Inspection cancelled from web by: Debby Ellis