ELE12-02982
| Final | 11/15/2016 | 11/15/2016 | 11/15/2016 3:39:31 PM | P | FAIL |
|
|
Call Tom for final walk down of Garage. Phone #: ###-#### Inspection requested via web by Tom Betty 110.3- Some general purpose receptacle outlets not working due to damage from construction. 1 circuit showed open neutral. 300.4- Flex connector cover on transformer T-DPAMPH missing. Exposed wiring subfect to physical damage. 300.15(A)- LB covers shall remain accessible after installation. Main level LB fitting 1/2 covered in concrete. 426.11- Grease tank in parking garage wrapped with heat trace cable shall have a barrier to protect from physical damage.
|
ELE16-01838
| Conference | 11/15/2016 | 11/15/2016 | 11/15/2016 3:39:05 PM | P | DONE |
|
|
Discussed with Brandon if temp occupancy could be granted to Annex 4th floor kitchen area. Explained all core and shell areas of building must be complete. All wiring shall be in an enclosure or box and shall not be subject to physical damage. All that is complete shall be tested.
|
ELE16-01838
| Final | 11/15/2016 | 11/15/2016 | 11/15/2016 3:05:15 PM | P | FAIL |
|
|
Level 9 TI POWER Partial Phone #: ###-#### Inspection requested via web by Tom Betty 110.3- Office 935-3 needs trimmed, open boxes, drywall repair in progress. 400.8- Flexible cords shall not penetrate ceilings. Flexible cords run from 9th floor to roof and in stairways. 605.5- Furniture connections shall be complete. Most have covers and receptacles missing. Furniture whips laying on floor with ends taped.
|
ELE16-03712
| Electrical Rough-In | 11/15/2016 | 11/15/2016 | 11/15/2016 1:09:45 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan wall rough in ok cover
|
ELE16-03353
| Electrical Rough-In | 11/14/2016 | 11/15/2016 | 11/15/2016 10:51:00 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Accelerator control room walls rough in ok cover
|
ELE16-03696
| Rough-In Permanent Service | 11/14/2016 | 11/15/2016 | 11/15/2016 10:30:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Charles Davis Rough in ok cover p/s u/g n ok
|
ELE16-03554
| Rough-In Permanent Service | 11/14/2016 | 11/15/2016 | 11/15/2016 9:55:02 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE16-03555
| Rough-In Permanent Service | 11/15/2016 | 11/15/2016 | 11/15/2016 9:24:57 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE16-03665
| Electrical Rough-In | 11/14/2016 | 11/15/2016 | 11/15/2016 8:50:00 AM | A | PASS |
|
|
Ok to cover interior, overhead service not finished till siders finish. Phone #: ###-#### Inspection requested via web by Robert Schroder Rough in ok cover
|