ELE16-03394
| Final | 11/15/2016 | 11/15/2016 | 11/16/2016 9:15:35 AM | A | PASS |
|
|
Von is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...
ok to final
|
ELE16-03667
| Final | 11/10/2016 | 11/15/2016 | 11/15/2016 3:04:39 PM | P | NR |
|
|
Any questions please call Calvin ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan....
need called in after power reconnected
|
ELE16-03667
| Permanent Service | 11/10/2016 | 11/15/2016 | 11/15/2016 3:03:53 PM | P | PASS |
|
|
Any questions please call Calvin ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan....
p/s u/g 4 meters rec ok
|
ELE16-03630
| Rough-In Permanent Service | 11/15/2016 | 11/15/2016 | 11/15/2016 2:08:08 PM | P | PASS |
|
|
late afternoon if possible please. Phone #: ###-#### Inspection requested via web by Tracy Robertson....
rough cover wall and truss ceiling ok p/s n ok
|
ELE16-03244
| Final | 11/15/2016 | 11/15/2016 | 11/15/2016 12:11:54 PM | P | PASS |
|
|
Door code dch Corrections fixed. Phone #: ###-#### Inspection requested via web by Greg Idsinga....
corrections made....ok to final
|
ELE16-03701
| Conference | 11/14/2016 | 11/15/2016 | 11/15/2016 11:39:04 AM | A | PASS |
|
|
Travis Phone #: ###-####....
discussed panel change, grounding, wire sizeing, sub panel, meter attachment
|
ELE16-02328
| Final | 11/14/2016 | 11/15/2016 | 11/15/2016 10:04:11 AM | A | FAIL |
|
|
Rocky Phone #: ###-####...
breaker lockouts need installed on hardwired appliances....d/w and hood
jaquzzi tub outlets need moved so readily accessible, within 1' of access....680.73
GFI for jaquzzi tub circuits need to be readily accessible....680.71
|
ELE16-03699
| Temporary Service | 11/14/2016 | 11/15/2016 | 11/15/2016 8:44:06 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson....
t/s u/g n ok
|
ELE16-03512
| Final | 11/14/2016 | 11/15/2016 | 11/15/2016 8:19:11 AM | A | PASS |
|
|
Eric Phone #: ###-####....ok to final
|
ELE16-03697
| Temporary Service | 11/14/2016 | 11/15/2016 | 11/15/2016 8:07:22 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt....
t/s u/g n ok
|