Inspections for the day of: Tuesday, November 15, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS16-00357 DOC - Permit Finaled11/15/201611/15/201611/15/2016 3:53:25 PMPPASS
The home owner installed a combustion air grill in the door to the laundry to allow it to communicate with the rest of the house. Doing so stopped the water heater flue from back drafting and solved the issue.
MEC16-03692 Rough-in11/14/201611/15/201611/15/2016 3:31:06 PMPPART
Request for cover inspection and light test on grease duct. Please contact job lead, Larry, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - light test pass on the north hood duct connection
MEC16-02501 Rough-in11/15/201611/15/201611/15/2016 3:30:12 PMPPART
Request for cover inspection 5th Fl. Corridor on Myrtle and Capital sides of the building. Please contact job lead, Larry, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover cooridoor ceiling on myrtle side of building
MEC16-04301 Final11/15/201611/15/201611/15/2016 2:39:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Marisa Hone
MEC16-01669 Conference11/14/201611/15/201611/15/2016 11:01:30 AMADONE
Request for conference with Dave Hannah, structural inspector, and mechanical inspector to discuss need of sheet rock in areas. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - they are going to fur out the wall above the drop ceiling to allow the 4" elbows to be installed and not crushed or altered
MEC16-05072 Final11/14/201611/15/201611/15/2016 10:04:02 AMAFAIL
Please call Sean Hyten before you go there.
Also, front gauge is under the fire pit there is a door on the side that opens Phone #: ###-#### Inspection requested via web by Sean Hyten - Gas piping not holding pressure, gauge down to 5lbs. Outdoor gas piping needs to be supported a minimum of 3 1/2" above the ground
MEC16-04814 Final11/14/201611/15/201611/15/2016 9:16:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Tim Petsche
MEC16-04999 Final11/14/201611/15/201611/15/2016 9:02:57 AMAPASS
Please call Alan at ###-#### before arriving, thank you. Phone #: ###-#### Inspection requested via web by TERESA HUTTO
MEC16-04628 Rough-in11/14/201611/15/201611/15/2016 8:46:30 AMAPASS
Please call Ted, thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
MEC16-02501 Rough-in11/14/201611/15/201611/15/2016 7:28:42 AMPCANC
Request for cover inspection 5th Fl corridor on Myrtle and Capital sides of building. Cover inspection for rooms on Myrtle side of the building. Please contact job lead, Larry, ###-####, with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
MEC15-02759 Conference11/15/201611/15/201611/15/2016 12:00:00 AMPPASS
Inspection of rerouting of vent to the roof of block 22 building, per code alternate. Passed inspections per Chad.