MIS16-00357
| DOC - Permit Finaled | 11/15/2016 | 11/15/2016 | 11/15/2016 3:53:25 PM | P | PASS |
|
|
The home owner installed a combustion air grill in the door to the laundry to allow it to communicate with the rest of the house. Doing so stopped the water heater flue from back drafting and solved the issue.
|
MEC16-03692
| Rough-in | 11/14/2016 | 11/15/2016 | 11/15/2016 3:31:06 PM | P | PART |
|
|
Request for cover inspection and light test on grease duct. Please contact job lead, Larry, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - light test pass on the north hood duct connection
|
MEC16-02501
| Rough-in | 11/15/2016 | 11/15/2016 | 11/15/2016 3:30:12 PM | P | PART |
|
|
Request for cover inspection 5th Fl. Corridor on Myrtle and Capital sides of the building. Please contact job lead, Larry, ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - okay to cover cooridoor ceiling on myrtle side of building
|
MEC16-04301
| Final | 11/15/2016 | 11/15/2016 | 11/15/2016 2:39:55 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Marisa Hone
|
MEC16-01669
| Conference | 11/14/2016 | 11/15/2016 | 11/15/2016 11:01:30 AM | A | DONE |
|
|
Request for conference with Dave Hannah, structural inspector, and mechanical inspector to discuss need of sheet rock in areas. Please contact job lead, Rob, ###-####, with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - they are going to fur out the wall above the drop ceiling to allow the 4" elbows to be installed and not crushed or altered
|
MEC16-05072
| Final | 11/14/2016 | 11/15/2016 | 11/15/2016 10:04:02 AM | A | FAIL |
|
|
Please call Sean Hyten before you go there. Also, front gauge is under the fire pit there is a door on the side that opens Phone #: ###-#### Inspection requested via web by Sean Hyten - Gas piping not holding pressure, gauge down to 5lbs. Outdoor gas piping needs to be supported a minimum of 3 1/2" above the ground
|
MEC16-04814
| Final | 11/14/2016 | 11/15/2016 | 11/15/2016 9:16:40 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tim Petsche
|
MEC16-04999
| Final | 11/14/2016 | 11/15/2016 | 11/15/2016 9:02:57 AM | A | PASS |
|
|
Please call Alan at ###-#### before arriving, thank you. Phone #: ###-#### Inspection requested via web by TERESA HUTTO
|
MEC16-04628
| Rough-in | 11/14/2016 | 11/15/2016 | 11/15/2016 8:46:30 AM | A | PASS |
|
|
Please call Ted, thank YOU! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
MEC16-02501
| Rough-in | 11/14/2016 | 11/15/2016 | 11/15/2016 7:28:42 AM | P | CANC |
|
|
Request for cover inspection 5th Fl corridor on Myrtle and Capital sides of building. Cover inspection for rooms on Myrtle side of the building. Please contact job lead, Larry, ###-####, with any questions or concerns. Phone #: ###-#### >> Inspection requested via web by Heather Gransbery Inspection cancelled from web by: Heather Gransbery
|
MEC15-02759
| Conference | 11/15/2016 | 11/15/2016 | 11/15/2016 12:00:00 AM | P | PASS |
|
|
Inspection of rerouting of vent to the roof of block 22 building, per code alternate. Passed inspections per Chad.
|