ELE17-01337
| Electrical Rough-In | 11/14/2017 | 11/15/2017 | 11/15/2017 3:01:21 PM | P | PART |
|
|
We are requesting a rough-in inpsection for the 2nd floor rooms, stairwell 1 and we are also requesting a consult inspection for the roof for tomorrow afternoon. Our contact is Rick @ ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate Stair 1 not ready, West of grid line 12 roof OK to wire below. Units 202 thru 218 rough in ok cover.
|
ELE16-03931
| Electrical Rough-In | 11/15/2017 | 11/15/2017 | 11/15/2017 2:02:38 PM | P | PASS |
|
|
Dropped lids in Elevator Lobbies 333, 433,533,633,733 Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted signed off in office drop lids. Rough in ok cover
|
ELE16-03932
| Electrical Rough-In | 11/15/2017 | 11/15/2017 | 11/15/2017 1:58:32 PM | P | PASS |
|
|
Thrash rooms dropped ceilings 338,438,538,638,738 Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted trash rooms drop lids signed off in office. Rough in ok cover
|
ELE17-02610
| Final | 11/14/2017 | 11/15/2017 | 11/15/2017 12:51:31 PM | A | PASS |
|
|
Garage code 0654E. Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|
ELE17-03822
| Final | 11/13/2017 | 11/15/2017 | 11/15/2017 10:17:01 AM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON No answer at door. Called, will recall
|
ELE17-03066
| Electrical Rough-In | 11/14/2017 | 11/15/2017 | 11/15/2017 10:00:02 AM | A | PASS |
|
|
We are requesting a above ceiling inspection for tomorrow morning. Our contact is Bryant @ ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Clint Tate Kitchen grid rough in ok cover
|
ELE17-02099
| Electrical Rough-In | 11/14/2017 | 11/15/2017 | 11/15/2017 9:55:25 AM | A | PASS |
|
|
Harlan Phone #: ###-#### Horizontal runs located at back of garage not covered and shall be covered for final. Rough in ok cover
|
ELE17-03791
| Final | 11/14/2017 | 11/15/2017 | 11/15/2017 9:15:13 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters 250.142- Grounded conductor shall not be connected to non-current carrying metal parts on load side of service disconnecting means. Old disconnecting means under meter has equipment ground tapped off grounded conductor in this box.
|
ELE17-03791
| Permanent Service | 11/14/2017 | 11/15/2017 | 11/15/2017 9:08:56 AM | A | PASS |
|
|
New Service inspection Phone #: ###-#### Inspection requested via web by Celinda Winters p/s u/g rec ok
|
ELE17-03856
| Electrical Rough-In | 11/14/2017 | 11/15/2017 | 11/15/2017 8:46:35 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake Phase 1 south end lounge, office, 2 exam walls rough in ok cover
|