Inspections for the day of: Wednesday, November 15, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04463 FIRE-Final Inspection11/15/201711/15/201711/15/2017 2:42:07 PMPPASS
life safety passed
FIR17-00329 INSP-Sprinkler Rough-in/Hydro11/14/201711/15/201711/15/2017 2:23:08 PMPCANC
Wrong permit called in.

Tom Phone #: ###-####
BLD17-01662 FIRE-Final Inspection11/15/201711/15/201711/15/2017 1:46:05 PMPPASS
Life safety passed.

Jim Phone #: ###-####
BLD17-00926 FIRE-Final Inspection11/14/201711/15/201711/15/2017 11:04:45 AMAPART
A temp for life safety is ok with Scott until both opticon systems at the two gates have been tested.

dale Phone #: ###-####
FIR17-00538 INSP-Final Inspection11/15/201711/15/201711/15/2017 9:46:03 AMPPASS
Permit finaled
FIR17-00352 INSP-Sprinkler Rough-in11/14/201711/15/201711/15/2017 9:45:05 AMAFAIL
Resubmit plans showing all of the additional 90's on the first floor to verify that the hydraulic calculations still work. Also the plans need to be "mirrored" because piping and room layout is backwards. Also I'm requesting insulation to be installed below the piping in the garage and as per the general contractor he will do the installation. No piping can be covered.