Inspections for the day of: Wednesday, November 15, 2017.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00623 INSP-Sprinkler Rough-in/Hydro11/15/201711/15/201711/15/2017 10:09:17 AMAPASS
Hydrostatic test for new fire sprinkler piping installed in tenant space complete. Rough to cover inspection for overhead fire sprinkler piping located above hardlids complete, area of work approved for cover.
BLD17-00460 FIRE-Final Inspection11/14/201711/15/201711/15/2017 9:37:50 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
FIR16-00758 INSP-Final Inspection11/14/201711/15/201711/15/2017 9:20:07 AMACANC
Fire alarm inspection could not be done due to underground supply to building not being turned on, inspection will need to be rescheduled. This inspection request is cancelled.
FIR16-00508 INSP-Final Inspection11/14/201711/15/201711/15/2017 8:49:00 AMAFAIL
Upright head in riser room is to far down from the deck. Underground supply is not on so not testing of fire sprinkler associated devices could be tested (Underground valve must be turned on by SUEZ). Riser brace needs to be attached to the floor.