FIR17-00623
| INSP-Sprinkler Rough-in/Hydro | 11/15/2017 | 11/15/2017 | 11/15/2017 10:09:17 AM | A | PASS |
|
|
Hydrostatic test for new fire sprinkler piping installed in tenant space complete. Rough to cover inspection for overhead fire sprinkler piping located above hardlids complete, area of work approved for cover.
|
BLD17-00460
| FIRE-Final Inspection | 11/14/2017 | 11/15/2017 | 11/15/2017 9:37:50 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
|
FIR16-00758
| INSP-Final Inspection | 11/14/2017 | 11/15/2017 | 11/15/2017 9:20:07 AM | A | CANC |
|
|
Fire alarm inspection could not be done due to underground supply to building not being turned on, inspection will need to be rescheduled. This inspection request is cancelled.
|
FIR16-00508
| INSP-Final Inspection | 11/14/2017 | 11/15/2017 | 11/15/2017 8:49:00 AM | A | FAIL |
|
|
Upright head in riser room is to far down from the deck. Underground supply is not on so not testing of fire sprinkler associated devices could be tested (Underground valve must be turned on by SUEZ). Riser brace needs to be attached to the floor.
|