FIR08-00387
| FIR-Aging Inspection | 11/15/2019 | 11/15/2019 | 11/18/2019 12:00:00 AM | | PEND |
|
|
|
BLD19-01638
| FIRE-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 2:28:56 PM | P | PASS |
|
|
Previously noted items have been corrected, fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided on permit sign off card for associated trades.
|
FIR19-00644
| INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 2:24:40 PM | P | FAIL |
|
|
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.
As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00643
| INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 2:24:26 PM | P | FAIL |
|
|
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.
As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00641
| INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 2:24:11 PM | P | FAIL |
|
|
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.
As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00639
| INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 2:23:57 PM | P | FAIL |
|
|
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.
As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00645
| INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 2:23:42 PM | P | FAIL |
|
|
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.
As early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00854
| INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 2:23:11 PM | P | PASS |
|
|
Final fire sprinkler ispection for area of work complete.
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
BLD19-01427
| FIRE-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 1:58:00 PM | P | PART |
|
|
Final life fire safety inspection for phase 2 complete.
John Phone #: ###-####
|
FIR19-00646
| INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 1:57:59 PM | P | FAIL |
|
|
Manufactures specs for fire panel requires the panel to be in an environment conditioned between 32 degrees fahrenheit to 120 degrees fahrenheit, provide conditioning in fire panel enclosure as discussed, conditioning has been provided for communicator encloser, heat detectors can remain in current location.
FAs early as possible Phone #: 2088990672 >> Inspection requested via mobile web by Josiah
|
FIR19-00843
| INSP-Sprinkler Rough-in | 11/14/2019 | 11/15/2019 | 11/15/2019 11:13:51 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in scope of work complete, approved for cover.
Contact Tanner Loomis - ###-#### 30 min prior to RTC Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00804
| INSP-Final Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 10:18:23 AM | P | CANC |
|
|
Reference notes entered on 01APR2019, address still has FIR permits in issued status for dry systems (FIR18-00719) as well as AES communicator that failed last inspection (FIR18-00161). Point of contact has been informed of related FIR permits that need to be followed up on before this permit can be finaled.
on is the field contact. Thanks for all you do! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00808
| INSP-Final Inspection | 11/14/2019 | 11/15/2019 | 11/15/2019 9:40:34 AM | A | FAIL |
|
|
Called point of contact listed, no answer, left a message. Could not get access to area, could not locate city approved drawings, no rough in inspection requested.
call ahead //Rick Phone #: ###-####
|
BLD19-02554
| FIRE-Final Inspection | 11/13/2019 | 11/15/2019 | 11/15/2019 9:25:06 AM | A | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signatures provided for associated trades on permit card.
Phone #: 2088415809 >> Inspection requested via mobile web by Mike
|
FIR19-00802
| INSP-Final Inspection | 11/12/2019 | 11/15/2019 | 11/15/2019 9:23:55 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00824
| INSP-Final Inspection | 11/12/2019 | 11/15/2019 | 11/15/2019 9:23:24 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
Please call 1/2 hour prior. Thanks Phone #: ###-#### Inspection requested via web by Rick Groom
|
FIR19-00593
| INSP-Final Inspection | 11/14/2019 | 11/15/2019 | 11/15/2019 6:55:10 AM | A | CANC |
|
|
Call before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|