MEC19-04324
| Rough-in | 11/15/2019 | 11/15/2019 | 11/15/2019 4:06:17 PM | P | PART |
|
|
Please contact Glen with any issues ###-#### Phone #: ###-#### Inspection requested via web by Yvonne Bowman - partial R/I ok on exhaust and fresh air ducting through roof - all mech work will be exposed and can be seen once installed
|
MEC19-05187
| Rough-in | 11/15/2019 | 11/15/2019 | 11/15/2019 3:18:47 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Sheldon Lebow - fireplace R/I ok
|
MEC19-05184
| Final | 11/15/2019 | 11/15/2019 | 11/15/2019 3:18:33 PM | P | FAIL |
|
|
Phamash Phone #: ###-#### - line set penetration needs sealed - A/C service ports need locking caps installed - furnace flue needs b vent installed where combustibles are closer than 6" - coil secondary condensate needs a wet switch installed -gas line needs sediment trap installed - couldn't access crawl builder said crawl access will be available at next inspection to check condensate and line set support
|
MEC19-04497
| Final | 11/12/2019 | 11/15/2019 | 11/15/2019 2:36:53 PM | P | PASS |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 1:30 PM. Contact for Right Now is Mary ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette - 5lb flue ok - final ok
|
MEC19-04855
| Final | 11/15/2019 | 11/15/2019 | 11/15/2019 1:58:16 PM | P | FAIL |
|
|
Gener ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks - one RTU needs flue extension installed - three furnaces need venting finished and installed per Man specs
|
MEC19-05186
| Pressure Test | 11/15/2019 | 11/15/2019 | 11/15/2019 1:55:55 PM | P | FAIL |
|
|
If there are any issues, can you call Tom at this number? Phone #: ###-#### Inspection requested via web by Nat Golden - this house doesn't have a gas line installed. thinking address is wrong for this permit. Called Tom and left voice mail
|
MEC19-04626
| Final | 11/15/2019 | 11/15/2019 | 11/15/2019 1:54:37 PM | P | PASS |
|
|
If there are any issues, can you call Tom at this number? Phone #: ###-#### Inspection requested via web by Nat Golden
|
MEC19-03990
| Rough-in | 11/13/2019 | 11/15/2019 | 11/15/2019 11:20:54 AM | A | FAIL |
|
|
cover Phone #: ###-#### Inspection requested via web by Brandon Sorensen - 1st floor ceiling cover not ready. Talked with contractor about items that need finished
|
MEC19-03035
| Final | 11/14/2019 | 11/15/2019 | 11/15/2019 10:45:57 AM | A | PASS |
|
|
Contact jasper with any questions Phone #: ###-#### Inspection requested via web by Ted Dumont - RTU final ok
|
MEC19-05142
| Rough-in | 11/14/2019 | 11/15/2019 | 11/15/2019 10:21:21 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - hard lid R/I ok
|
MEC19-04780
| Final | 11/13/2019 | 11/15/2019 | 11/15/2019 10:11:30 AM | A | FAIL |
|
|
call ahead to Chris @ ###-#### to make sure he can be home for inspector entry. Phone #: ###-#### Inspection requested via web by Angie Maguire - furnace combustion air pipe needs connect to furnace - coil needs wet switch installed - tankless water heater needs flue venting installed with primer and glue. right now the intake looks glued and the exhaust isn't glue at all.
|
MEC19-01757
| Final | 11/14/2019 | 11/15/2019 | 11/15/2019 9:52:01 AM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - need TAB report for final
|
MEC19-04754
| Final | 11/13/2019 | 11/15/2019 | 11/15/2019 9:29:19 AM | A | FAIL |
|
|
PLEASE CALL HOMEOWNER KERRY WHEN IN ROUTE- SHE WORKS NIGHTS AND ASKED IF YOU CAN COME OUT ANYTIME AFTER 930A- I ADVISED THAT WE COULDNT GUARANTEE THAT BUT WE COULD CERTAINLY ASK NICELY TO SEE IF THE INSPECTOR ASSIGNED CAN ACCOMMODATE Phone #: ###-#### Inspection requested via web by Rick Montgomery - furnace ac coil co ok - need to see electrical permit
|
MEC19-02427
| Conference | 11/14/2019 | 11/15/2019 | 11/15/2019 9:08:23 AM | A | CANC |
|
|
Please Call Kyle @ ###-#### 45 min prior to arrival so he can meet inspector on site. Thank you. Phone #: ###-#### Inspection requested via web by Ashley Shoecraft
|
MEC19-04412
| Final | 11/14/2019 | 11/15/2019 | 11/15/2019 8:55:17 AM | A | PASS |
|
|
Please call Dave with any questions @ ###-#### Phone #: ###-#### Inspection requested via web by Dave DeChambeau - tab report ok - final ok
|
MEC19-04806
| Final | 11/14/2019 | 11/15/2019 | 11/15/2019 8:34:16 AM | A | PASS |
|
|
Diffuser replacement inspection Phone #: ###-#### Inspection requested via web by RaChelle Frisbee - final ok
|
MEC19-05101
| Final | 11/14/2019 | 11/15/2019 | 11/15/2019 8:00:45 AM | A | PASS |
|
|
Locking caps have been put on and line set has been supported. Call Brett if you have any questions ###-#### Phone #: ###-#### Inspection requested via web by Brett Shannon - final ok
|
MEC19-01814
| Mec-Aging Inspection | 11/15/2019 | 11/15/2019 | 11/15/2019 8:00:06 AM | | PASS |
|
|
WIP
|