BLD04-00871
| FIRE-Final Inspection | 11/15/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | A | FAIL |
|
|
Repair two emergency lights and final fire alarm 11/16/2004 10:07:51 AM
|
BLD04-00871
| FIRE-Alarm Testing | 11/15/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | A | FAIL |
|
|
Duct detector shut down wired wrong and supervisory signal were not sent in 11/16/2004 10:08:43 AM
|
BLD04-01918
| FIRE-Final Inspection | 11/15/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | A | FAIL |
|
|
Repair two emergency lights and final fire alarm 11/16/2004 10:09:18 AM
|
BLD04-01918
| FIRE-Alarm Testing | 11/15/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | A | FAIL |
|
|
Repair two emergency lights and final fire alarm 11/16/2004 10:09:26 AM
|
BLD04-00959
| FIRE-Final Inspection | 11/15/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 11/16/2004 9:58:49 AM
|
FIR04-00686
| INSP-Final Inspection | 11/15/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | A | PASS |
|
|
Fire sprinklers finaled 11/16/2004 10:09:43 AM
|
FIR04-00682
| INSP-Final Inspection | 11/16/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | A | FAIL |
|
|
Duct detectors did not shut down hvac unit immediately. Monitoring station did not receive supervisory signals
|
FIR04-00368
| INSP-Sprinkler Rough-in | 11/15/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | P | PART |
|
|
Hydro test for 1st-4th floors plus the dry system is ok. See plans for piping in an overbuild that is too far from deck. Need tenting inspection and letter from structural engineer. Club house has not been tested or inspected. 11/16/2004 3:19:32 PM
|
FIR04-00693
| INSP-Alarm Testing | 11/16/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled 11/16/2004 1:48:46 PM
|
FIR04-00682
| INSP-Final Inspection | 11/16/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | P | CANC |
|
|
To be rescheduled 11/16/2004 3:38:24 PM
|
FIR04-00479
| INSP-Alarm Testing | 11/15/2004 | 11/16/2004 | 11/16/2004 12:00:00 AM | P | FAIL |
|
|
Duct smoke detectors for hvac units 5 and 6 are still not placed per NFPA 72 11/16/2004 3:31:09 PM
|