Inspections for the day of: Tuesday, November 16, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00871 FIRE-Final Inspection11/15/200411/16/200411/16/2004 12:00:00 AMAFAIL
Repair two emergency lights and final fire alarm 11/16/2004 10:07:51 AM
BLD04-00871 FIRE-Alarm Testing11/15/200411/16/200411/16/2004 12:00:00 AMAFAIL
Duct detector shut down wired wrong and supervisory signal were not sent in 11/16/2004 10:08:43 AM
BLD04-01918 FIRE-Final Inspection11/15/200411/16/200411/16/2004 12:00:00 AMAFAIL
Repair two emergency lights and final fire alarm 11/16/2004 10:09:18 AM
BLD04-01918 FIRE-Alarm Testing11/15/200411/16/200411/16/2004 12:00:00 AMAFAIL
Repair two emergency lights and final fire alarm 11/16/2004 10:09:26 AM
BLD04-00959 FIRE-Final Inspection11/15/200411/16/200411/16/2004 12:00:00 AMAPASS
fire life safety finaled 11/16/2004 9:58:49 AM
FIR04-00686 INSP-Final Inspection11/15/200411/16/200411/16/2004 12:00:00 AMAPASS
Fire sprinklers finaled 11/16/2004 10:09:43 AM
FIR04-00682 INSP-Final Inspection11/16/200411/16/200411/16/2004 12:00:00 AMAFAIL
Duct detectors did not shut down hvac unit immediately. Monitoring station did not receive supervisory signals
FIR04-00368 INSP-Sprinkler Rough-in11/15/200411/16/200411/16/2004 12:00:00 AMPPART
Hydro test for 1st-4th floors plus the dry system is ok. See plans for piping in an overbuild that is too far from deck. Need tenting inspection and letter from structural engineer. Club house has not been tested or inspected. 11/16/2004 3:19:32 PM
FIR04-00693 INSP-Alarm Testing11/16/200411/16/200411/16/2004 12:00:00 AMPPASS
Fire alarm finaled 11/16/2004 1:48:46 PM
FIR04-00682 INSP-Final Inspection11/16/200411/16/200411/16/2004 12:00:00 AMPCANC
To be rescheduled 11/16/2004 3:38:24 PM
FIR04-00479 INSP-Alarm Testing11/15/200411/16/200411/16/2004 12:00:00 AMPFAIL
Duct smoke detectors for hvac units 5 and 6 are still not placed per NFPA 72 11/16/2004 3:31:09 PM