MIS05-00199
| FIR-Final | 11/16/2005 | 11/16/2005 | 11/17/2005 10:09:24 AM | P | FAIL |
|
|
Need to provide current inspection tags for the fire extinguishers, provide current annual inspection on the fire sprinkler system.
|
FIR05-00453
| INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 4:37:58 PM | P | CANC |
|
|
###-#### - grant Note: after 3:00 pm after school Cancel inspection per phone conversation, schedules for inspection time did not correlate. To be completed at a later date.
|
FIR05-00335
| INSP-Alarm Testing | 11/16/2005 | 11/16/2005 | 11/16/2005 4:25:38 PM | P | DONE |
|
|
Inspection scheduled to determine status of permit.
|
BLD05-02396
| FIRE-Final Inspection | 11/16/2005 | 11/16/2005 | 11/16/2005 4:23:14 PM | P | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00592
| INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 4:21:58 PM | P | FAIL |
|
|
One hanger at armover above room adjacent to the break room is overspaced.
|
FIR05-00591
| INSP-Final Inspection | 11/16/2005 | 11/16/2005 | 11/16/2005 4:20:34 PM | P | FAIL |
|
|
The hanger on one armover is overspaced, one head at column is not installed as shown on plans-however it appears to be superfluous per the required spacing of 168 sq. ft. which is met without the head.
|
BLD05-01980
| FIRE-Alarm Testing | 11/16/2005 | 11/16/2005 | 11/16/2005 3:56:37 PM | P | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00726
| INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 2:43:16 PM | P | PART |
|
|
Overhead sprinkler work is complete and satisfactory, final pending shell sprinker final approval.
|
FIR05-00681
| INSP-Sprinkler Rough-in/Hydro | 11/15/2005 | 11/16/2005 | 11/16/2005 2:41:25 PM | P | FAIL |
|
|
Hydrostatic test not completed due to leakage per contractor.
|
FIR05-00681
| INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 2:40:24 PM | P | NR |
|
|
This permit is not ready for final at this time.
|
FIR05-00681
| INSP-Sprinkler Rough-in | 11/15/2005 | 11/16/2005 | 11/16/2005 2:39:32 PM | P | FAIL |
|
|
One head is overspaced as circled on plans, one head is too close to a heat diffuser for the supplied temp rating, need canopies and tile and hydrostatic test pre final.
|
FIR05-00688
| INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 2:36:16 PM | A | PART |
|
|
Sprinkler work is satisfactory, final pending final approval of shell sprinkler permit.
|
FIR05-00694
| INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 2:34:38 PM | A | PART |
|
|
Final pending resubmittals showing added heads under ductwork and shell sprinkler final approval.
|
MIS05-00212
| FIR-Final | 11/15/2005 | 11/16/2005 | 11/16/2005 11:30:06 AM | A | FAIL |
|
|
Provide an additional fire extinguisher for the seating area, remove two surface bolts at the back doors as discussed, repair emergency light at front counter.
|
BLD05-02730
| FIRE-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 11:06:22 AM | A | PASS |
|
|
Fire life safety passed inspection, alarm and sprinkler permits are finaled.
|
FIR05-00332
| INSP-Sprinkler Rough-in | 11/15/2005 | 11/16/2005 | 11/16/2005 10:39:08 AM | A | PART |
|
|
Basement kitchen area rough-in is good for cover.
|
FIR05-00765
| INSP-Sprinkler Rough-in | 11/15/2005 | 11/16/2005 | 11/16/2005 9:59:06 AM | A | PART |
|
|
Overhead rough-in is acceptable to cover, will final when ceiling tile and escutcheons are installed and paper/tape is removed from all heads.
|
BLD05-02938
| FIRE-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 9:25:12 AM | A | PASS |
|
|
Items on correction notice have been completed, fire life safety passed inspection.
|
FIR05-00694
| INSP-Sprinkler Rough-in/Hydro | 11/15/2005 | 11/16/2005 | 11/16/2005 8:42:33 AM | A | CANC |
|
|
Duplicate inspection already called in.
|
FIR05-00668
| INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 8:40:59 AM | A | PASS |
|
|
Hood suppression system operated correctly under test conditions.
|
FIR05-00686
| INSP-Final Inspection | 11/16/2005 | 11/16/2005 | 11/16/2005 12:00:00 AM | A | PASS |
|
|
Fire alarm permit finaled.
|