MIS05-00110
| MIS-Aging Inspection | 11/16/2005 | 11/16/2005 | 11/21/2005 4:36:46 PM | | CANC |
|
|
|
FIR05-00569
| INSP-Sprinkler Rough-in/Hydro | 11/15/2005 | 11/16/2005 | 11/17/2005 7:42:10 AM | P | PART |
|
|
Hydro test for the first floor piping passed. First floor rough-in passed.
|
FIR05-00589
| INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/17/2005 7:41:39 AM | A | FAIL |
|
|
Need to provide verification of battery backup for the dialer/HUB
|
FIR05-00210
| INSP-Alarm Testing | 11/15/2005 | 11/16/2005 | 11/16/2005 3:38:19 PM | A | FAIL |
|
|
Sample tubes are incorrect. The holes in the tubes as installed are 10" apart. Per Mark at Silent Knight tech support the holes on the 2.5 should be 2" o. c. and the 5.0 and 10.0 should be 3" o.c.
|
FIR05-00716
| INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 10:44:16 AM | A | FAIL |
|
|
harry; Phone #: ###-#### A sprinkler armover at the rear door has been hung from electrical conduit. Take to building structure. Insulation is falling from the deck and obstructing the upright sprinklers. This will need to be repaired. Pendant heads through out the space are exceed the max 130sq. ft spacing. Fix it. I would have marked locations on the plans had 1/2 of the floor plan not be missing.
|
BLD05-01392
| FIRE-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 10:22:56 AM | A | PASS |
|
|
Life safety finaled
|