Inspections for the day of: Thursday, November 16, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02929 ELE-Aging Inspection11/16/200611/16/200611/20/2006 7:39:12 AM PART
wsuc
ELE06-03414 ELE-Aging Inspection11/16/200611/16/200611/20/2006 7:38:39 AM PART
wsuc
ELE06-02599 Final11/16/200611/16/200611/17/2006 11:23:45 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Dan Rohl
ELE06-02957 Electrical Rough-In11/15/200611/16/200611/16/2006 4:17:55 PMAPART
Don, reinspection; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt walls ok only
ELE06-03354 Rough-In Permanent Service11/15/200611/16/200611/16/2006 3:51:28 PMAPASS
Phone #: ###-#### Internet Inspection Request from: Tracy
r/i all 4 units, p/s u/g new ok
ELE06-02694 Final11/16/200611/16/200611/16/2006 3:05:33 PMPPASS
mike - please call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
ELE06-04279 Final11/16/200611/16/200611/16/2006 2:39:54 PMPNR
Mike, access thru left side of garage; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called left message needs r/i not final ?
ELE06-03743 Electrical Rough-In11/15/200611/16/200611/16/2006 2:29:09 PMAPART
any questions please call Ed Schallock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford one outlet in mri rm note all wiring shall meet 517.13(A&B)
ELE06-04280 Electrical Rough-In11/16/200611/16/200611/16/2006 2:09:27 PMPPART
security wall only anop
ELE06-04280 Electrical Rough-In11/16/200611/16/200611/16/2006 2:08:26 PMPFAIL
wall cover; Phone #: ###-#### Internet Inspection Request from: Don Spackman
called corr , 314.16 box fill handy boxes used at show window outlets, 300.11 raceway shall not support phone cable at panel, 300.4 nail plates and 11/4" parallel 358.30 and 330.30 secure raceways and cables within 3ft for emt 12" for MC, noted to general about bi level switching told him to contact structual inspector
ELE06-01951 Final11/16/200611/16/200611/16/2006 1:03:31 PMPPASS
This Final is a re-do of failed final on 11/9/06; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok
ELE06-01950 Final11/16/200611/16/200611/16/2006 1:03:12 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok
ELE06-03777 Final11/15/200611/16/200611/16/2006 10:20:31 AMAPASS
chris ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
ok
ELE06-04179 Electrical Rough-In11/15/200611/16/200611/16/2006 10:18:48 AMAPART
don-- note: uffer ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok forf fdirt
ELE06-03168 Final11/15/200611/16/200611/16/2006 9:17:59 AMANR
chad ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
called
ELE06-03603 Final11/15/200611/16/200611/16/2006 9:17:36 AMANR
chad ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
called
ELE06-04229 Temporary Service11/15/200611/16/200611/16/2006 9:17:13 AMAPASS
Scheduled by a contractor via Hello! on 11/15/2006 at 1:29:12 PM. Contact: ###-####. t/s u/g new ok