Inspections for the day of: Thursday, November 16, 2006.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04126 Rough-In Permanent Service11/16/200611/16/200611/17/2006 5:17:09 AMPCANC
any questions please call Jesse Collingsworth; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
ELE06-03369 Final11/16/200611/16/200611/16/2006 4:17:33 PMPFAIL
larry ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith callwd, nec 312.5 all conductors entering enclosures shall have abrasion protection, pecpt shall be gfci protected
ELE06-04278 Electrical Rough-In11/16/200611/16/200611/16/2006 4:15:47 PMPCANC
READY FOR INSPECTION OF METER BASE AND PANEL ALONG WITH NEW OUTLETS, LIGHTING, PHONE, AND TV. LOCK BOX IS ON THE TEMPORAY POWER POLE OUT BACK AND THE CODE IS 1290. ANY QUESTIONS PLEASE CALL BRIAN AT ###-####.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called, see rip
ELE06-03400 Final11/16/200611/16/200611/16/2006 4:12:07 PMPPASS
Scheduled by a contractor via Hello! on 11/16/2006 at 7:34:34 AM. Contact: ###-####. ok to final
ELE06-03797 Electrical Rough-In11/15/200611/16/200611/16/2006 3:11:54 PMPPASS
paul Note: ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover ceiling
ELE06-04277 Temporary Service11/16/200611/16/200611/16/2006 2:29:03 PMPPASS
Internet Inspection Request from: Don Lustig t/s o/h n ok
ELE06-04237 Electrical Rough-In11/16/200611/16/200611/16/2006 1:54:39 PMPPASS
dustin; Phone #: ###-#### Please call 1/2 hr prior to inspeciton Internet Inspection Request from: Cathy Chiles called, left survey for 1/14" 2 plcs, told contr to add 2 rooms to permit, left message
ELE06-02104 Permanent Service11/16/200611/16/200611/16/2006 1:29:49 PMPPASS
Service ready for inspection Internet Inspection Request from: Don Lustig p/s u/g n ok
ELE06-04275 Permanent Service11/16/200611/16/200611/16/2006 12:38:39 PMPPASS
space 13 bud ###-#### p/s o/h rec ok
ELE06-03905 Electrical Rough-In11/15/200611/16/200611/16/2006 10:54:22 AMAPASS
hz; Phone #: ###-#### Internet Inspection Request from: Patricia Smith main floor and basement ric ok
ELE06-04217 Conference11/15/200611/16/200611/16/2006 10:36:42 AMPCANC
Scheduled by a contractor via Hello! on 11/15/2006 at 11:43:09 AM. Contact: ###-####. done in am
ELE06-04069 Final11/16/200611/16/200611/16/2006 10:36:18 AMPPART
doug; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles elect shall fix subpanel grounding, provide drip protection, finish lighting over cash wrap, and sign ckt, will check flat type recpts in wiremold
ELE06-04217 Conference11/15/200611/16/200611/16/2006 10:34:24 AMADONE
Scheduled by a contractor via Hello! on 11/15/2006 at 2:49:07 PM. Contact: ###-####. told elect to open clg for inspection and no violations shall be retained
ELE06-04238 Final11/15/200611/16/200611/16/2006 10:33:32 AMAPASS
Scheduled by a contractor via Hello! on 11/15/2006 at 2:46:15 PM. Contact: ###-####. ok to final
ELE06-02254 Permanent Service11/15/200611/16/200611/16/2006 10:33:10 AMAPASS
Scheduled by a contractor via Hello! on 11/15/2006 at 7:26:36 PM. Contact: ###-####. p/s u/g n ok
ELE06-03275 Permanent Service11/15/200611/16/200611/16/2006 10:32:41 AMAPASS
Scheduled by a contractor via Hello! on 11/15/2006 at 7:25:14 PM. Contact: ###-####. p/s u/g n ok, new line-up
ELE06-03680 Final11/15/200611/16/200611/16/2006 9:25:44 AMAPASS
Ed, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE06-00867 Final11/15/200611/16/200611/16/2006 9:15:31 AMAPASS
Any questions ask for Mike Johsnon.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz talked to contr, ok to final work on this permit
ELE06-03185 Permanent Service11/15/200611/16/200611/16/2006 9:14:04 AMAFAIL
PERMANENT SERVICE; Phone #: ###-#### x1 Internet Inspection Request from: BRIAN KEITH called contr to reverse ground and neutral in service panel
ELE06-04271 Permanent Service11/15/200611/16/200611/16/2006 9:00:10 AMAFAIL
###-#### randall--service is outside talked to owner, said to call when done, nec 250.52(A) shall ground water pipe coming in, 250.52(A)(5) rod electrodes shall be 8" long,250.53(B) rod electrodes shall be 6" apart, 200.6 shall id grounded conductor, 408.4 shall complete panel schedule
ELE06-04155 Electrical Rough-In11/15/200611/16/200611/16/2006 8:30:25 AMAPASS
INSPECTION FOR TRENCH FOR COVER IN AM; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH u/g ok to cover
ELE06-04269 Permanent Service11/15/200611/16/200611/16/2006 8:20:19 AMAPASS
NEED TO GET THE SERVICEFOR TEMP POWER Internet Inspection Request from: Bob Glenn called, left survey, left message, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be completed, p/s o/h rec ok