ELE06-04126
| Rough-In Permanent Service | 11/16/2006 | 11/16/2006 | 11/17/2006 5:17:09 AM | P | CANC |
|
|
any questions please call Jesse Collingsworth; Phone #: ###-#### Internet Inspection Request from: Jeff Radford
|
ELE06-03369
| Final | 11/16/2006 | 11/16/2006 | 11/16/2006 4:17:33 PM | P | FAIL |
|
|
larry ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith callwd, nec 312.5 all conductors entering enclosures shall have abrasion protection, pecpt shall be gfci protected
|
ELE06-04278
| Electrical Rough-In | 11/16/2006 | 11/16/2006 | 11/16/2006 4:15:47 PM | P | CANC |
|
|
READY FOR INSPECTION OF METER BASE AND PANEL ALONG WITH NEW OUTLETS, LIGHTING, PHONE, AND TV. LOCK BOX IS ON THE TEMPORAY POWER POLE OUT BACK AND THE CODE IS 1290. ANY QUESTIONS PLEASE CALL BRIAN AT ###-####.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called, see rip
|
ELE06-03400
| Final | 11/16/2006 | 11/16/2006 | 11/16/2006 4:12:07 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/16/2006 at 7:34:34 AM. Contact: ###-####. ok to final
|
ELE06-03797
| Electrical Rough-In | 11/15/2006 | 11/16/2006 | 11/16/2006 3:11:54 PM | P | PASS |
|
|
paul Note: ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover ceiling
|
ELE06-04277
| Temporary Service | 11/16/2006 | 11/16/2006 | 11/16/2006 2:29:03 PM | P | PASS |
|
|
Internet Inspection Request from: Don Lustig t/s o/h n ok
|
ELE06-04237
| Electrical Rough-In | 11/16/2006 | 11/16/2006 | 11/16/2006 1:54:39 PM | P | PASS |
|
|
dustin; Phone #: ###-#### Please call 1/2 hr prior to inspeciton Internet Inspection Request from: Cathy Chiles called, left survey for 1/14" 2 plcs, told contr to add 2 rooms to permit, left message
|
ELE06-02104
| Permanent Service | 11/16/2006 | 11/16/2006 | 11/16/2006 1:29:49 PM | P | PASS |
|
|
Service ready for inspection Internet Inspection Request from: Don Lustig p/s u/g n ok
|
ELE06-04275
| Permanent Service | 11/16/2006 | 11/16/2006 | 11/16/2006 12:38:39 PM | P | PASS |
|
|
space 13 bud ###-#### p/s o/h rec ok
|
ELE06-03905
| Electrical Rough-In | 11/15/2006 | 11/16/2006 | 11/16/2006 10:54:22 AM | A | PASS |
|
|
hz; Phone #: ###-#### Internet Inspection Request from: Patricia Smith main floor and basement ric ok
|
ELE06-04217
| Conference | 11/15/2006 | 11/16/2006 | 11/16/2006 10:36:42 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 11/15/2006 at 11:43:09 AM. Contact: ###-####. done in am
|
ELE06-04069
| Final | 11/16/2006 | 11/16/2006 | 11/16/2006 10:36:18 AM | P | PART |
|
|
doug; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles elect shall fix subpanel grounding, provide drip protection, finish lighting over cash wrap, and sign ckt, will check flat type recpts in wiremold
|
ELE06-04217
| Conference | 11/15/2006 | 11/16/2006 | 11/16/2006 10:34:24 AM | A | DONE |
|
|
Scheduled by a contractor via Hello! on 11/15/2006 at 2:49:07 PM. Contact: ###-####. told elect to open clg for inspection and no violations shall be retained
|
ELE06-04238
| Final | 11/15/2006 | 11/16/2006 | 11/16/2006 10:33:32 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/15/2006 at 2:46:15 PM. Contact: ###-####. ok to final
|
ELE06-02254
| Permanent Service | 11/15/2006 | 11/16/2006 | 11/16/2006 10:33:10 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/15/2006 at 7:26:36 PM. Contact: ###-####. p/s u/g n ok
|
ELE06-03275
| Permanent Service | 11/15/2006 | 11/16/2006 | 11/16/2006 10:32:41 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/15/2006 at 7:25:14 PM. Contact: ###-####. p/s u/g n ok, new line-up
|
ELE06-03680
| Final | 11/15/2006 | 11/16/2006 | 11/16/2006 9:25:44 AM | A | PASS |
|
|
Ed, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
|
ELE06-00867
| Final | 11/15/2006 | 11/16/2006 | 11/16/2006 9:15:31 AM | A | PASS |
|
|
Any questions ask for Mike Johsnon.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz talked to contr, ok to final work on this permit
|
ELE06-03185
| Permanent Service | 11/15/2006 | 11/16/2006 | 11/16/2006 9:14:04 AM | A | FAIL |
|
|
PERMANENT SERVICE; Phone #: ###-#### x1 Internet Inspection Request from: BRIAN KEITH called contr to reverse ground and neutral in service panel
|
ELE06-04271
| Permanent Service | 11/15/2006 | 11/16/2006 | 11/16/2006 9:00:10 AM | A | FAIL |
|
|
###-#### randall--service is outside talked to owner, said to call when done, nec 250.52(A) shall ground water pipe coming in, 250.52(A)(5) rod electrodes shall be 8" long,250.53(B) rod electrodes shall be 6" apart, 200.6 shall id grounded conductor, 408.4 shall complete panel schedule
|
ELE06-04155
| Electrical Rough-In | 11/15/2006 | 11/16/2006 | 11/16/2006 8:30:25 AM | A | PASS |
|
|
INSPECTION FOR TRENCH FOR COVER IN AM; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH u/g ok to cover
|
ELE06-04269
| Permanent Service | 11/15/2006 | 11/16/2006 | 11/16/2006 8:20:19 AM | A | PASS |
|
|
NEED TO GET THE SERVICEFOR TEMP POWER Internet Inspection Request from: Bob Glenn called, left survey, left message, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be completed, p/s o/h rec ok
|