FIR07-00672
| FIR-Aging Inspection | 11/16/2007 | 11/16/2007 | 11/16/2007 4:51:21 PM | | NR |
|
|
work is in progress
|
BLD04-00084
| FIRE-Final Inspection | 11/16/2007 | 11/16/2007 | 11/16/2007 4:48:49 PM | P | PASS |
|
|
Life safety passed
|
FIR07-00809
| INSP-Final Inspection | 11/15/2007 | 11/16/2007 | 11/16/2007 4:44:09 PM | P | FAIL |
|
|
Project is not ready for a final due to project related fire alarm and sprinkler permits needing finaled. I also found exit signs and emergency lights that did not function. Signs need to be posted at the property entrance.
|
FIR07-00782
| INSP-Sprinkler Rough-in/Hydro | 11/16/2007 | 11/16/2007 | 11/16/2007 4:37:14 PM | A | FAIL |
|
|
Overhead hydro test passed. The doghouses need inspected still. One head needs to be added between the two kitchen hoods. Two heads need to be extended in the north dining area to provide coverage under a soffit/decorative beam. Sprinkler coverage needs to be added in the new shed that is attached to the main building. The sprinkler contractor needs to contact Brian about installing galvanized piping on the roof of the structure for the additional dog house and the addition of the sprinkler head in the shed.
|
BLD07-01634
| FIRE-Final Inspection | 11/15/2007 | 11/16/2007 | 11/16/2007 4:30:40 PM | A | FAIL |
|
|
The correct remote annunciators need installed and the duct smoke detectors tested.
|
BLD07-02790
| FIRE-Final Inspection | 11/16/2007 | 11/16/2007 | 11/16/2007 4:30:03 PM | P | PASS |
|
|
Life safety passed.
|
BLD07-00772
| FIRE-Final Inspection | 11/15/2007 | 11/16/2007 | 11/16/2007 2:16:08 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 11/15/2007 at 5:03:07 PM. Contact: ###-####. I called the contact number and left a message about the fire sprinkler permit only having a rough-in inspection and no final at this time. Without a fire sprinkler final there can be no fire life safety sign off.
|
BLD07-02731
| FIRE-Final Inspection | 11/16/2007 | 11/16/2007 | 11/16/2007 1:56:24 PM | P | PASS |
|
|
Life safety passed.
|
FIR07-00386
| INSP-Alarm Testing | 11/15/2007 | 11/16/2007 | 11/16/2007 1:36:00 PM | A | CANC |
|
|
The fire alarm testing was canceled by the fire alarm contractor
|
BLD06-02010
| FIRE-Final Inspection | 11/15/2007 | 11/16/2007 | 11/16/2007 1:23:16 PM | A | CANC |
|
|
The fire alarm testing was canceled by the fire alarm contractor
|
FIR07-00449
| INSP-Sprinkler Rough-in | 11/15/2007 | 11/16/2007 | 11/16/2007 1:13:16 PM | A | PASS |
|
|
See the city approved plans for hard lid locationes where sprinkler piping is ok to cover.
|
BLD07-01225
| FIRE-Final Inspection | 11/15/2007 | 11/16/2007 | 11/16/2007 12:12:09 PM | A | FAIL |
|
|
Items such as the duct smoke detectors were not ready to test. No inspection was performed.
|
BLD07-00948
| FIRE-Final Inspection | 11/15/2007 | 11/16/2007 | 11/16/2007 12:04:38 PM | A | FAIL |
|
|
The project is not ready for a final yet but the ham hood is ok to use.
|
BLD07-02296
| FIRE-Final Inspection | 11/15/2007 | 11/16/2007 | 11/16/2007 11:44:38 AM | A | FAIL |
|
|
The emergency light still have not been repaired.
|
FIR07-00871
| INSP-Final Inspection | 11/14/2007 | 11/16/2007 | 11/16/2007 10:57:07 AM | A | PASS |
|
|
The cooking hood suppresson systems operated correctly.
|
BLD07-02974
| FIRE-Final Inspection | 11/15/2007 | 11/16/2007 | 11/16/2007 10:39:29 AM | A | FAIL |
|
|
The hood suppression system needs to be recertified. No inspection was performed due to no approved plans being on site.
|
FIR07-00770
| INSP-Alarm Testing | 11/15/2007 | 11/16/2007 | 11/16/2007 10:37:51 AM | A | DONE |
|
|
The ham hood system came in and went out correctly. The phone lines also tested ok. But the phone line troubles do not annunciate audibly at the annunciators and the zone descriptors for the NAC panels is not correct. Battery troubles do not annunciate at the panel either. I believe its a D113 module that needs to be added based on past experiences. This is all that was tested today.
|
FIR07-00777
| INSP-Final Inspection | 11/14/2007 | 11/16/2007 | 11/16/2007 10:34:08 AM | A | PASS |
|
|
Hood suppression system operated correctly. The additional nozzle has been added as discused.
|
BLD07-01226
| FIRE-Final Inspection | 11/15/2007 | 11/16/2007 | 11/16/2007 8:25:23 AM | A | PASS |
|
|
LIfe safety for the shell passed.
|
FIR07-00576
| INSP-Final Inspection | 11/14/2007 | 11/16/2007 | 11/16/2007 8:00:32 AM | A | PASS |
|
|
permit finaled
|