Inspections for the day of: Friday, November 16, 2007.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00672 FIR-Aging Inspection11/16/200711/16/200711/16/2007 4:51:21 PM NR
work is in progress
BLD04-00084 FIRE-Final Inspection11/16/200711/16/200711/16/2007 4:48:49 PMPPASS
Life safety passed
FIR07-00809 INSP-Final Inspection11/15/200711/16/200711/16/2007 4:44:09 PMPFAIL
Project is not ready for a final due to project related fire alarm and sprinkler permits needing finaled. I also found exit signs and emergency lights that did not function. Signs need to be posted at the property entrance.
FIR07-00782 INSP-Sprinkler Rough-in/Hydro11/16/200711/16/200711/16/2007 4:37:14 PMAFAIL
Overhead hydro test passed. The doghouses need inspected still. One head needs to be added between the two kitchen hoods. Two heads need to be extended in the north dining area to provide coverage under a soffit/decorative beam. Sprinkler coverage needs to be added in the new shed that is attached to the main building. The sprinkler contractor needs to contact Brian about installing galvanized piping on the roof of the structure for the additional dog house and the addition of the sprinkler head in the shed.
BLD07-01634 FIRE-Final Inspection11/15/200711/16/200711/16/2007 4:30:40 PMAFAIL
The correct remote annunciators need installed and the duct smoke detectors tested.
BLD07-02790 FIRE-Final Inspection11/16/200711/16/200711/16/2007 4:30:03 PMPPASS
Life safety passed.
BLD07-00772 FIRE-Final Inspection11/15/200711/16/200711/16/2007 2:16:08 PMPCANC
Scheduled by a contractor via Hello! on 11/15/2007 at 5:03:07 PM. Contact: ###-####. I called the contact number and left a message about the fire sprinkler permit only having a rough-in inspection and no final at this time. Without a fire sprinkler final there can be no fire life safety sign off.
BLD07-02731 FIRE-Final Inspection11/16/200711/16/200711/16/2007 1:56:24 PMPPASS
Life safety passed.
FIR07-00386 INSP-Alarm Testing11/15/200711/16/200711/16/2007 1:36:00 PMACANC
The fire alarm testing was canceled by the fire alarm contractor
BLD06-02010 FIRE-Final Inspection11/15/200711/16/200711/16/2007 1:23:16 PMACANC
The fire alarm testing was canceled by the fire alarm contractor
FIR07-00449 INSP-Sprinkler Rough-in11/15/200711/16/200711/16/2007 1:13:16 PMAPASS
See the city approved plans for hard lid locationes where sprinkler piping is ok to cover.
BLD07-01225 FIRE-Final Inspection11/15/200711/16/200711/16/2007 12:12:09 PMAFAIL
Items such as the duct smoke detectors were not ready to test. No inspection was performed.
BLD07-00948 FIRE-Final Inspection11/15/200711/16/200711/16/2007 12:04:38 PMAFAIL
The project is not ready for a final yet but the ham hood is ok to use.
BLD07-02296 FIRE-Final Inspection11/15/200711/16/200711/16/2007 11:44:38 AMAFAIL
The emergency light still have not been repaired.
FIR07-00871 INSP-Final Inspection11/14/200711/16/200711/16/2007 10:57:07 AMAPASS
The cooking hood suppresson systems operated correctly.
BLD07-02974 FIRE-Final Inspection11/15/200711/16/200711/16/2007 10:39:29 AMAFAIL
The hood suppression system needs to be recertified. No inspection was performed due to no approved plans being on site.
FIR07-00770 INSP-Alarm Testing11/15/200711/16/200711/16/2007 10:37:51 AMADONE
The ham hood system came in and went out correctly. The phone lines also tested ok. But the phone line troubles do not annunciate audibly at the annunciators and the zone descriptors for the NAC panels is not correct. Battery troubles do not annunciate at the panel either. I believe its a D113 module that needs to be added based on past experiences. This is all that was tested today.
FIR07-00777 INSP-Final Inspection11/14/200711/16/200711/16/2007 10:34:08 AMAPASS
Hood suppression system operated correctly. The additional nozzle has been added as discused.
BLD07-01226 FIRE-Final Inspection11/15/200711/16/200711/16/2007 8:25:23 AMAPASS
LIfe safety for the shell passed.
FIR07-00576 INSP-Final Inspection11/14/200711/16/200711/16/2007 8:00:32 AMAPASS
permit finaled