FIR04-00523
| FIR-Aging Inspection | 11/16/2010 | 11/16/2010 | 11/17/2010 2:56:06 PM | | NR |
|
|
Per Rod this permit is going to be voided.
|
FIR10-00470
| INSP-Sprinkler Rough-in/Hydro | 11/15/2010 | 11/16/2010 | 11/16/2010 3:33:10 PM | P | PASS |
|
|
The underground hydro test passed with leakage acceptable per NFPA 13 chapter 10. The underground flush passed. The overhead rough-in for the Service Bay/Product/Electrical Room passed with the exception of the redline corrections noted on the city approved plans which include the need for an aux. drain, missing flexible cplgs.
|
FIR09-00175
| FIR-Aging Inspection | 11/16/2010 | 11/16/2010 | 11/16/2010 2:55:41 PM | | NR |
|
|
work is in progress
|
FIR09-00117
| FIR-Aging Inspection | 11/16/2010 | 11/16/2010 | 11/16/2010 2:52:55 PM | | NR |
|
|
work is in progress
|
FIR09-00374
| INSP-Final Inspection | 11/16/2010 | 11/16/2010 | 11/16/2010 2:43:24 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00407
| INSP-Final Inspection | 11/16/2010 | 11/16/2010 | 11/16/2010 2:08:36 PM | P | PASS |
|
|
permit finaled
|
FIR09-00081
| INSP-Final Inspection | 11/16/2010 | 11/16/2010 | 11/16/2010 2:07:39 PM | P | FAIL |
|
|
All items are ok except the remote annunciator located at the west exit does not sound upon alarm, trouble or supervisory signals. A correction notice was left requesting the repair of this device.
|
BLD10-02521
| FIRE-Final Inspection | 11/12/2010 | 11/16/2010 | 11/16/2010 11:38:11 AM | A | PART |
|
|
A temporary occupancy was given with Scotts permission until the Knox box that is on order has been installed.
|