Inspections for the day of: Tuesday, November 16, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00523 FIR-Aging Inspection11/16/201011/16/201011/17/2010 2:56:06 PM NR
Per Rod this permit is going to be voided.
FIR10-00470 INSP-Sprinkler Rough-in/Hydro11/15/201011/16/201011/16/2010 3:33:10 PMPPASS
The underground hydro test passed with leakage acceptable per NFPA 13 chapter 10. The underground flush passed. The overhead rough-in for the Service Bay/Product/Electrical Room passed with the exception of the redline corrections noted on the city approved plans which include the need for an aux. drain, missing flexible cplgs.
FIR09-00175 FIR-Aging Inspection11/16/201011/16/201011/16/2010 2:55:41 PM NR
work is in progress
FIR09-00117 FIR-Aging Inspection11/16/201011/16/201011/16/2010 2:52:55 PM NR
work is in progress
FIR09-00374 INSP-Final Inspection11/16/201011/16/201011/16/2010 2:43:24 PMPPASS
Permit finaled
FIR09-00407 INSP-Final Inspection11/16/201011/16/201011/16/2010 2:08:36 PMPPASS
permit finaled
FIR09-00081 INSP-Final Inspection11/16/201011/16/201011/16/2010 2:07:39 PMPFAIL
All items are ok except the remote annunciator located at the west exit does not sound upon alarm, trouble or supervisory signals. A correction notice was left requesting the repair of this device.
BLD10-02521 FIRE-Final Inspection11/12/201011/16/201011/16/2010 11:38:11 AMAPART
A temporary occupancy was given with Scotts permission until the Knox box that is on order has been installed.