FIR11-00540
| INSP-Final Inspection | 11/9/2011 | 11/16/2011 | 11/17/2011 2:23:37 PM | P | PASS |
|
|
After hours fire alarm inspection completed. Scope of work passed, permit finaled.
|
FIR11-00522
| INSP-Final Inspection | 11/15/2011 | 11/16/2011 | 11/16/2011 4:52:43 PM | P | NR |
|
|
Regarding FACP location per NFPA 72 10.16.3.1 and 10.16.3.2, IFC 2009 605.3 and NFPA 70 guidelines.
|
FIR11-00582
| INSP-Sprinkler Rough-in | 11/15/2011 | 11/16/2011 | 11/16/2011 2:29:15 PM | A | PART |
|
|
Overhead work approved for ceiling cover. Noted field mods okayed.
|
FIR11-00397
| INSP-Final Inspection | 11/15/2011 | 11/16/2011 | 11/16/2011 2:11:01 PM | A | FAIL |
|
|
Missing backflow certification, control valves need locked or sealed in the open position, riser is not secured to the structure, inspectors test and drain does not terminate outside, noted leaking feed main in the crawlspace.
|
BLD10-01237
| FIRE-Final Inspection | 11/15/2011 | 11/16/2011 | 11/16/2011 12:49:20 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD11-00439
| FIRE-Final Inspection | 11/15/2011 | 11/16/2011 | 11/16/2011 12:47:48 PM | A | PASS |
|
|
Correction items verified for completion. Plan modifications reviewed, life safety final approved.
|