Inspections for the day of: Wednesday, November 16, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00540 INSP-Final Inspection11/9/201111/16/201111/17/2011 2:23:37 PMPPASS
After hours fire alarm inspection completed. Scope of work passed, permit finaled.
FIR11-00522 INSP-Final Inspection11/15/201111/16/201111/16/2011 4:52:43 PMPNR
Regarding FACP location per NFPA 72 10.16.3.1 and 10.16.3.2, IFC 2009 605.3 and NFPA 70 guidelines.
FIR11-00582 INSP-Sprinkler Rough-in11/15/201111/16/201111/16/2011 2:29:15 PMAPART
Overhead work approved for ceiling cover. Noted field mods okayed.
FIR11-00397 INSP-Final Inspection11/15/201111/16/201111/16/2011 2:11:01 PMAFAIL
Missing backflow certification, control valves need locked or sealed in the open position, riser is not secured to the structure, inspectors test and drain does not terminate outside, noted leaking feed main in the crawlspace.
BLD10-01237 FIRE-Final Inspection11/15/201111/16/201111/16/2011 12:49:20 PMAPASS
Fire life safety inspection passed.
BLD11-00439 FIRE-Final Inspection11/15/201111/16/201111/16/2011 12:47:48 PMAPASS
Correction items verified for completion. Plan modifications reviewed, life safety final approved.