Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC12-03716 Pressure Test11/14/201211/16/201211/16/2012 4:57:54 PMPFAIL
4:00-- Duct blast test at 9am Phone #: ###-#### >> Inspection requested via web by Debbie Marino...NOBODY SHOWED UP TO DO THE DUCT BLASTER...OOPS
MEC12-03716 Rough-in11/14/201211/16/201211/16/2012 4:41:44 PMPFAIL
04:00 - Duct blast test at 9am Phone #: ###-#### >> Inspection requested via web by Debbie Marino....NOBODY SHOWED UP FOR THE DUCT BLASTER
MEC12-04094 Pressure Test11/15/201211/16/201211/16/2012 4:40:52 PMPPART
JOB CONTACT KEITH ###-#### Phone #: ###-#### >> Inspection requested via web by MARGGIE BUSS...TEMPORARY LINE FROM 60LB METER TO BASEMENT AND UP TO 2ND FLOOR..ISOLATION VAVLE EVERY 3 FLOORS.
MEC12-04036 Final11/13/201211/16/201211/16/2012 3:37:09 PMPPASS
Contact homeowner for access ###-#### or Phone #: ###-#### >> Inspection requested via web by Amanda Drake
MEC12-04095 Rough-in11/16/201211/16/201211/16/2012 3:21:40 PMPPART
Oleg Phone #: ###-####...need stamped approved manual J on site...need rectangular to round transition on range vent....20lb gas ok
GCM12-00213 GCM-Rough In & Pressure Test11/14/201211/16/201211/16/2012 11:59:11 AMAPART
Debbie @ ###-####
Duct Blast Test at 11 a.m....20lb gas ok....need 1/4" slope per foot on furn flue...need 60' offset on w/h flue...protection plate not covering gas tite...equipment doesn't match manual J...duct blaster ok
GCM12-00201 GCM-Rough In & Pressure Test11/15/201211/16/201211/16/2012 10:53:23 AMAPASS
April @ ###-####....r/i and 20lb gas ok...duct blaster ok
GCM12-00200 GCM-Rough-in11/15/201211/16/201211/16/2012 10:52:30 AMAPASS
April @ ###-####...r/i and 20lb gas ok...duct blaster ok
MEC12-03948 Conference11/14/201211/16/201211/16/2012 9:55:14 AMAPASS
PER CONVERSATION W/ DIXIE, SHE WILL CONDUCT A LIGHT TEST ON FABRICATED GREASE DUCT AT RM MECHANICAL SHOP. ADDRESS IS 5998 W. GOWEN ROAD. TEST WILL BE READY BY 7:00 AM. CONTACT TONY MAGNUSON FOR QUESTIONS ###-####. Phone #: ###-#### >> Inspection requested via web by Allison Briggs...light test on all 18 guage welded stainless grease duct ok