Inspections for the day of: Friday, November 16, 2012.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00330 FIR-Aging Inspection11/16/201211/16/201211/20/2012 8:33:36 AM NR
work is in progress
FIR12-00231 INSP-Final Inspection11/15/201211/16/201211/16/2012 3:58:38 PMPPASS
Permit finaled. Hood suppression system functioned correctly.
FIR12-00658 INSP-Final Inspection11/16/201211/16/201211/16/2012 3:55:45 PMPCANC
Overbooked. Scott is going to reschedule for monday. Phone #: ###-####
BLD12-01747 FIRE-Final Inspection11/16/201211/16/201211/16/2012 3:55:12 PMPCANC
Overbooked. Jeremy is going to reschedule for monday morning. Phone #: ###-####
FIR12-00645 INSP-Final Inspection11/16/201211/16/201211/16/2012 3:51:04 PMPPART
A temporary occupancy was given with Scott Arellano's permission until the correct programming of the duct smoke detectors is accomplished with the monitoring company. All other items have been corrected. The hvac units had not previously been wired for shut down but are now.
FIR12-00668 INSP-Final Inspection11/16/201211/16/201211/16/2012 3:47:54 PMPPASS
Permit finaled
BLD10-01983 FIRE-Final Inspection11/15/201211/16/201211/16/2012 3:36:47 PMPFAIL
Repair the exit signs and emergency lights as marked on the plans. Remove the dead bolt from the rear warehouse door. Provide single action hardware on the restroomdoors.
BLD12-02631 FIRE-Final Inspection11/16/201211/16/201211/16/2012 2:34:21 PMPFAIL
Provide city approved plans and remove the deadbolt from the door between the office and warehouse area.
BLD12-02535 FIRE-Final Inspection11/15/201211/16/201211/16/2012 2:18:57 PMPFAIL
Provide modified sprinkler protection in office area. This work requires separate permit. Provide racking permit for the storage racks that exceed 8'-0" in height and remove dead bolt lock from the rear warehouse door.
BLD12-01069 FIRE-Final Inspection11/16/201211/16/201211/16/2012 12:43:21 PMPPASS
Life safety passed. Panic hardware was installed on the east end exit door.
FIR12-00494 INSP-Final Inspection11/16/201211/16/201211/16/2012 12:14:43 PMPPASS
Permit finaled
BLD12-01789 FIRE-Final Inspection11/15/201211/16/201211/16/2012 12:13:52 PMAFAIL
Life safety will be ok to pass when the shell core permit is finaled, panic hardware installed on the rear exit door and the project related fire alarm permit is finaled.
FIR12-00645 INSP-Final Inspection11/15/201211/16/201211/16/2012 12:04:40 PMAFAIL
The fire alarm control panel only has one phone line, monitoring is not set up correctly (no alarm or supervisory signals were received), hvac units did not shut down upon detection of smoke and as-builts are needed showing the additional tamper switch as well as the smoke detector above the ceiling.
FIR12-00618 INSP-Final Inspection11/15/201211/16/201211/16/2012 11:51:17 AMACANC
Cancel per jeff Phone #: ###-####
BLD12-01915 FIRE-Final Inspection11/16/201211/16/201211/16/2012 12:00:00 AMPPART
rick - life safety Phone #: ###-#### //temp occ ok, will be ok for perm when fire alarm permit is addressed.