Inspections for the day of: Thursday, November 16, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03878 Conference11/15/201711/16/201711/17/2017 1:45:33 PMPDONE
Matt cell ###-#### Phone #: ###-#### Inspection requested via web by Matthew White
Discussed service change needed for the addition of solar to shop. ELE17-03542 for solar. Meter main to be installed on shop and subfeeding 200 amp shop panel in garage and subfeed house off garage panel. Only chase between shop and house is an unused 3" plumbing ABS pipe. As long as wiring method is rated for direct burial ABS ok to use. A pull box or gutter to be installed at floor level in garage and at house so ABS is not use as exposed electrical raceway. No splice below 18" inside garage. Old fused panel in garage to be turned into a junction point for shop circuits. Not rewiring or adding wiring to shop area all existing wiring ok to remain. At house panel location over landing on stairway the 30" by 36" work space present. This was verbally communicated. A grounding electrode system, disconnecting means and seperation of grounds and neutrals shall be complete at house.
ELE17-00761 Final11/16/201711/16/201711/16/2017 4:07:52 PMPPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
Final ok
ELE17-03140 Electrical Rough-In11/16/201711/16/201711/16/2017 3:21:46 PMPFAIL
Jason Wells is contact on this project at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
NO BLD permit found. Spoke with rep and stated architect still working on plans. Unable to inspect due to BLD permit issue. 330.30- MC shall be secured with in 12" of a box.
362.30- ENT shall be secured with in 3' of a box.
Verbal with contact
ELE17-03834 Electrical Rough-In11/16/201711/16/201711/16/2017 3:06:00 PMPPASS
Requesting a partial rough in inspection, located on the east end of the building. I will meet on site, we will have a check off plan available for the inspector to show inspection locations. Thanks Kurt Phone #: ###-#### Inspection requested via web by Kurt Carlson
As noted on contractor print wall rough in east of lobby rough in ok cover.
ELE17-02949 Final11/16/201711/16/201711/16/2017 2:35:47 PMPPASS
210.8(B)- All 120 volt, 15 and 20 amp receptacle outlets located with in 6'''''''' of a sink shall have GFCI protection. 7 dedicated for warming chairs, microwaves, refrigerators. 11/16: These outlets have been replaced by John Rowles Phone #: ###-#### Inspection requested via web by Kevin Perez Final ok
ELE17-01032 Electrical Rough-In11/15/201711/16/201711/16/2017 11:32:54 AMAPART
Rough in for Cover
1st floor soffit in Units 107, 108, 109, 110, 111, 112, 114.
4th floor corridor, Area 3
Contact Scott Wilson
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
111 not ready, 107 thru 110, 112, 114 drop lids and 4th floor corridor walls only rough in ok cover
ELE17-02949 Final11/15/201711/16/201711/16/2017 10:36:43 AMAFAIL
John Phone #: ###-####
210.8(B)- All 120 volt, 15 and 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection. 7 dedicated for warming chairs, microwaves, refrigerators.
Verbal with contact on site.
ELE17-03811 Electrical Rough-In11/14/201711/16/201711/16/2017 10:03:32 AMAFAIL
WIRING WAS FOR BASEMENT REMODEL ONLY, ALL OTHER WIRING INCLUDING SERVICE AND PANEL IN BASEMENT WHERE EXISTING. FOR ACCESS FIND LOCKBOX ON RAILING AT BOTTOM OF LAMP, USE ACCESS CODE 3704. PLEASE CONTACT ALLEN THE ELECTRICIAN FOR ANY QUESTIONS ###-#### Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON
110.26- Minimum work space shall be provided for panel board. 30" wide 36" deep. Panel in basement located behind framed wall ith studs 16" on center.
300.4- Where cables are run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected ftom physical damage by nail plates. Marked by X.
314.29- Boxes located behind framed wall. Box in net panel and box located below net panel shall be accessible.
330.12- MC shall not be installed wher subject to physical damage. Corners cut MC may be damaged when drywall installed.
330.30- MC shall be secured with in 12" of a box.
Contact stated general contractor had conversation with electrical inspector about workspace issue and inspector OK with not providing work space. Will address issue with 375 when he returns.
ELE17-03682 Final11/15/201711/16/201711/16/2017 9:03:59 AMAPASS
If door is locked call steve for access ###-#### Phone #: ###-#### Inspection requested via web by steve sellers Final ok