Inspections for the day of: Thursday, November 16, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01744 ELE-Aging Inspection11/16/201711/16/201711/20/2017 10:37:21 AM FAIL
No responce to notice
ELE17-02457 Final11/16/201711/16/201711/16/2017 2:29:10 PMPNH
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Recall with access code
ELE17-00870 Final11/16/201711/16/201711/16/2017 2:09:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Victor Kelley Final ok
ELE16-01382 Final11/16/201711/16/201711/16/2017 12:07:57 PMPPASS
Aging Phone #: ###-#### Inspection requested via web by Steve VanWinkle sign final ok
ELE17-03847 Final11/15/201711/16/201711/16/2017 12:06:13 PMPPASS
Corrected issues as discussed with inspector. Please contact with any concerns. Lock box is #1516. Thank you Phone #: ###-#### Inspection requested via web by Cortney Hopper corrections made final ok
ELE17-03435 Electrical Rough-In11/16/201711/16/201711/16/2017 11:39:53 AMPPASS
Please inspect floor heat in master and down stairs bathroom. Please call me a half an hour before inspection to insure access. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Floor heat only ok to cover
ELE17-03863 Permanent Service11/15/201711/16/201711/16/2017 11:20:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Matthew White p/s o/h n ok
ELE17-03885 Temporary Service11/16/201711/16/201711/16/2017 10:54:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson t/s u/g n ok
ELE16-03797 Final11/15/201711/16/201711/16/2017 10:54:33 AMAFAIL
james Phone #: ###-#### 110.3 Reverse polarity on Recep. to Rt of fireplace. 210.8A7 Recep to right of Mudroom sink needs GFCI. 210.8A6 Kitchen counter receps need GFCI. 314.20 Kitchen Backsplash receps need Sparkrings. 352.30A Service riser needs stapped above slip joint. 356.30 A/C flex needs strapped within 12in of disconnect.422.30 Furnace needs disc. 110.24 36in x 36in platform needs constructed in front of meter.
ELE17-03666 Permanent Service11/15/201711/16/201711/16/2017 8:44:53 AMAPASS
Inspection for meter without power for more than 1 year Phone #: ###-#### Inspection requested via web by steve ragan p/s o/h rec ok
ELE16-02745 Electrical Rough-In11/16/201711/16/201711/16/2017 12:00:00 AMAFAIL
4th and fifth floor hallway grid
510-520
301-310 Phone #: ###-#### Inspection requested via web by Kenneth Chapman List of items with Fred/ Forman