Inspections for the day of: Thursday, November 16, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF17-00072 INSP-Final11/14/201711/16/201711/16/2017 2:50:40 PMPFAIL
System failed to operate.

Zach Phone #: ###-#### Inspection requested via web by Don Kartchner
FIR17-00541 INSP-Sprinkler Rough-in/Hydro11/16/201711/16/201711/16/2017 1:46:42 PMPFAIL
No approved plans on site. No inspection performed

Rick Phone #: ###-####
FIR17-00352 INSP-Sprinkler Rough-in11/16/201711/16/201711/16/2017 10:43:47 AMPPASS
Rough-in passed. Tenting passed. Piping is ok to cover
BLD17-01593 FIRE-Final Inspection11/15/201711/16/201711/16/2017 9:19:07 AMAFAIL
All items have been corrected except for the second fire extinguisher has not been installed as discussed. Management wants to discuss with fire dept. Re-inspection fee accessed.

Elle Phone #: ###-####
FIR17-00432 INSP-Sprinkler Rough-in/Hydro11/16/201711/16/201711/16/2017 9:13:35 AMPPART
24 hour air test started at 9:00am with 43psi on guage.
FIR17-00432 INSP-Sprinkler Rough-in/Hydro11/15/201711/16/201711/15/2017 2:24:25 PMAPASS
Overhead rough-in and hydro test passed. I need verification that the air compressor is ok and the outside combustible canopies are meet NFPA 13 8.15.7

tom Phone #: ###-####