Inspections for the day of: Monday, November 17, 2003.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00532 INSP-Final Inspection11/14/200311/17/200311/17/2003 12:00:00 AMAFAIL
contractor did not have keys to riser room 11/17/2003 9:59:18 AM
FIR03-00206 INSP-Sprinkler Rough-in/Hydro11/17/200311/17/200311/17/2003 12:00:00 AMPPART
the two uprights and two pendants in the connecting area are ok to cover. I notified Gerald with Treasure Valley Fire that it looks like a upright head will be required in the mechanical chase unless they can meet exception 12 of concealed combustible spaces 11/17/2003 2:19:27 PM
FIR03-00550 INSP-Final Inspection11/17/200311/17/200311/17/2003 12:00:00 AMPPASS
PAT CELL PHONE; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
FIR03-00640 INSP-Sprinkler Rough-in/Hydro11/17/200311/17/200311/17/2003 12:00:00 AMPPART
pendant heads in hard lid areas ok to cover 11/17/2003 3:02:39 PM
FIR03-00600 INSP-Sprinkler Rough-in/Hydro11/17/200311/17/200311/17/2003 12:00:00 AMPFAIL
above ground hydro test failed 11/17/2003 3:07:41 PM
FIR03-00403 INSP-Final Inspection11/17/200311/17/200311/17/2003 12:00:00 AMPPASS
FIR03-00390 INSP-Final Inspection11/17/200311/17/200311/17/2003 12:00:00 AMPPASS
BLD03-01810 FIRE-Final Inspection11/17/200311/17/200311/17/2003 12:00:00 AMPPASS
fire life safety and fire sprinkler finaled
BLD03-01880 FIRE-Final Inspection11/17/200311/17/200311/17/2003 12:00:00 AMPPASS
fire life safety finaled
BLD03-02163 FIRE-Final Inspection11/17/200311/17/200311/17/2003 12:00:00 AMPPASS
Fire alarm finaled. OK for permanent occupancy
FIR03-00548 INSP-Final Inspection11/17/200311/17/200311/17/2003 12:00:00 AMPPASS
inspection finaled under FIR03-00550
BLD03-01739 FIRE-Final Inspection11/17/200311/17/200311/17/2003 12:00:00 AMPPASS
fire life safety finaled
FIR03-00482 INSP-Final Inspection11/12/200311/17/200311/17/2003 12:00:00 AMPFAIL
tested the first smoke detector and one of the door magnets did not release. No other devices tested 11/17/2003 3:58:20 PM
FIR03-00524 INSP-Final Inspection11/13/200311/17/200311/17/2003 12:00:00 AMPFAIL
joe; Phone #: ###-#### Did not test the system since the manual pull is less than 10' from the hood and needs relocated 11/17/2003 1:09:09 PM
FIR03-00524 INSP-Final Inspection11/13/200311/17/200311/17/2003 12:00:00 AMPCANC
duplicate inspection 11/17/2003 1:09:33 PM
BLD03-02103 FIRE-Final Inspection11/14/200311/17/200311/17/2003 12:00:00 AMPCANC
earl; Phone #: ###-#### I spoke to Earl and he wanted to cancel the inspection due to doors not being installed as yet 11/17/2003 10:23:16 AM