ELE05-03040
| ELE-Aging Inspection | 11/17/2005 | 11/17/2005 | 11/21/2005 9:51:41 AM | | FAIL |
|
|
called cor. 600.5(C)(3),and 410.15(B)
|
ELE05-04182
| Temporary Service | 11/17/2005 | 11/17/2005 | 11/17/2005 4:03:42 PM | P | PASS |
|
|
bob-- ###-#### t/s o/h new ok
|
ELE05-03697
| Electrical Rough-In | 11/16/2005 | 11/17/2005 | 11/17/2005 3:26:38 PM | P | NR |
|
|
david/belina; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles need to meet owner too many things wrong ,and p/s was install in violation by prior owner, no violations to be retained called owner will schedule conference, box fill wall spacing, bath circuit has other outlets on it romex pulled in pvc, derate wires needs to update permit for 5 rms not 2
|
ELE05-03082
| Permanent Service | 11/17/2005 | 11/17/2005 | 11/17/2005 2:22:46 PM | P | PASS |
|
|
p/s u/g new ok for hook up and house meter
|
ELE05-04183
| Final | 11/17/2005 | 11/17/2005 | 11/17/2005 1:25:02 PM | P | PASS |
|
|
Jay ###-####///please call when on way so can meet you there ok cor. made
|
ELE05-04185
| Electrical Rough-In | 11/17/2005 | 11/17/2005 | 11/17/2005 12:51:38 PM | P | PASS |
|
|
###-#### - mike r/i
|
ELE05-04114
| Temporary Service | 11/17/2005 | 11/17/2005 | 11/17/2005 12:09:21 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/17/2005 at 9:38:16 AM. Contact: ###-####. t/s u/g new ok
|
ELE03-00484
| Final | 11/17/2005 | 11/17/2005 | 11/17/2005 11:03:54 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/17/2005 at 6:08:52 AM. Contact: ###-####. ok
|
ELE05-02764
| Final | 11/16/2005 | 11/17/2005 | 11/17/2005 10:32:43 AM | A | PASS |
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE05-04173
| Final | 11/16/2005 | 11/17/2005 | 11/17/2005 10:04:04 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/16/2005 at 1:18:35 PM. Contact: ###-####. called u/g not proper depth, 18" for pvc, 24" for uf
|
ELE05-04153
| Temporary Service | 11/16/2005 | 11/17/2005 | 11/17/2005 9:40:32 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 11/16/2005 at 1:22:45 PM. Contact: ###-####. cor. called 300.10 tighten all fitting and lugs, locknuts ,bond bushing, 312.5 conn for GEC, 110.12 clean t/s, 110.14 all strands of conductor grd wire under acorn clamp
|
ELE05-04124
| Rough-In Permanent Service | 11/16/2005 | 11/17/2005 | 11/17/2005 9:37:58 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/16/2005 at 10:53:45 AM. Contact: ###-####. r/i ok p/s u/g new ok
|
ELE05-04134
| Temporary Service | 11/16/2005 | 11/17/2005 | 11/17/2005 9:37:14 AM | A | PART |
|
|
Re-inspection after corrections made. Contact is Perry.; Phone #: ###-#### Internet Inspection Request from: David Bonner needs to wire job shack t/s o/h new ok for hook up
|
ELE05-04185
| Permanent Service | 11/17/2005 | 11/17/2005 | 11/17/2005 12:00:00 AM | P | PASS |
|
|
###-#### - mike p/s u/g rec. ok
|
ELE05-03082
| Permanent Service | 11/17/2005 | 11/17/2005 | 11/17/2005 12:00:00 AM | P | PASS |
|
|
meter pack inspection only, please; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney p/s u/g new ok and house meter
|