Inspections for the day of: Friday, November 17, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03349 Rough-In Permanent Service11/17/200611/17/200611/17/2006 4:27:33 PMPDONE
Phone #: ###-#### x0960 Internet Inspection Request from: Tracy Robertson
was done 11-01-06
ELE06-03164 Final11/16/200611/17/200611/17/2006 4:19:28 PMAPASS
rhonda ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
ok no card
ELE06-03560 Final11/14/200611/17/200611/17/2006 4:19:02 PMAPASS
Scheduled by a contractor via Hello! on 11/14/2006 at 12:03:06 PM. Contact: ###-####. ok
ELE06-04303 Electrical Rough-In11/16/200611/17/200611/17/2006 3:19:58 PMAPART
Scheduled by a contractor via Hello! on 11/16/2006 at 7:06:17 PM. Contact: ###-####. walls ok
ELE06-04304 Electrical Rough-In11/16/200611/17/200611/17/2006 3:19:37 PMAPART
Scheduled by a contractor via Hello! on 11/16/2006 at 7:04:24 PM. Contact: ###-####. walls ok
ELE06-03637 Final11/17/200611/17/200611/17/2006 3:19:14 PMPCANC
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS needs final for shell core bld before ele can be finaled called
ELE06-02599 Final11/17/200611/17/200611/17/2006 2:13:41 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Rohl 210.52 (C)(1) shall provide proper spacing for counter top in din rm, 110.3(B) manufactures instruction 15 amp circuits for each jtub system, wall heater not allowed in wet location and does not meet manufactures clearence rquirements called
ELE06-04305 Temporary Service11/17/200611/17/200611/17/2006 1:13:18 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire t/s u/g new ok, called left message needs conn for GEC and clean dir from t/s
ELE06-04227 Electrical Rough-In11/17/200611/17/200611/17/2006 1:12:12 PMPFAIL
Mike; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
corr. called 210.11(C)(2)&52(F) all recepts in laundry shall be on laundry circuit, 314.16 box fill , 300.4 nail plates and 11/4", 110.12(A) relace all plastic boxes with extra KOs broken out, cables sheath shall extent into box 1/4"314.20 boxes not flush furred out wall, 300.14 6" free length
ELE06-03724 Electrical Rough-In11/17/200611/17/200611/17/2006 12:25:32 PMPFAIL
###-#### corr. met owner, 300.4(A)(1)&(D) nail plates and 11/4" for holes and cables, 314.20 outside boxes shall be flush with siding, 210.52(A) outlet fixed panel of sliding door wall space, 110.3(B) wire jtub per manufactures instructions, 210.11(C)(3)&52(D) 20 amp bath circuit and location for outlet bathrm, strip sheath from romex and makeup of boxes 6" free lenght, staple cables within 8" ok boxes
ELE06-04149 Permanent Service11/17/200611/17/200611/17/2006 11:51:42 AMPPASS
roy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g rec. ok
ELE06-04149 Final11/17/200611/17/200611/17/2006 11:51:22 AMPPASS
roy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE06-04305 Temporary Service11/16/200611/17/200611/17/2006 11:19:30 AMACANC
Scheduled by a contractor via Hello! on 11/16/2006 at 4:07:30 PM. Contact: ###-####.
ELE06-04307 Electrical Rough-In11/16/200611/17/200611/17/2006 8:44:33 AMAPART
ceiling cover rough-in, please contact Toby, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters

ceiling and walls front half of store
ELE06-03724 Electrical Rough-In11/16/200611/17/200611/17/2006 8:43:44 AMAFAIL
after 9am please//Billie ###-#### metr owner will post correction
ELE06-03349 Final11/17/200611/17/200611/17/2006 7:51:17 AMPCANC
Thank You!!; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
ELE06-04279 Electrical Rough-In11/16/200611/17/200611/16/2006 3:52:24 PMAPASS
###-#### - mike ok called shall not use screws in plastic box outside 2 gang