ELE06-03662
| Final | 11/16/2006 | 11/17/2006 | 11/17/2006 4:26:05 PM | A | PASS |
|
|
corrections made. Ask for Greg when calling.; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney corr made, ok to final
|
ELE06-04118
| Electrical Rough-In | 11/17/2006 | 11/17/2006 | 11/17/2006 4:04:48 PM | P | PART |
|
|
darrell Note: 2nd floor hallway or ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles reviewed securing requirements for relocated lv wiring and new elec above clgs, ok to cover clgs in south hall, 2nd floor
|
ELE06-02364
| Electrical Rough-In | 11/17/2006 | 11/17/2006 | 11/17/2006 4:02:33 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 11/17/2006 at 10:03:24 AM. Contact: ###-####. recpt area walls ok to cover
|
ELE06-04312
| Rough-In Permanent Service | 11/17/2006 | 11/17/2006 | 11/17/2006 3:57:12 PM | P | CANC |
|
|
neal; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong type inspection request, see p/s
|
ELE06-04312
| Permanent Service | 11/17/2006 | 11/17/2006 | 11/17/2006 3:55:45 PM | P | PASS |
|
|
neal; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles calleed, told contr to drive in gnd rods and secure gec, contr said this bldg only slab, no footings, p/s u/g n ok
|
ELE06-03378
| Final | 11/16/2006 | 11/17/2006 | 11/17/2006 3:10:46 PM | P | FAIL |
|
|
for questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/ Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer told elect, left corr notice, nec 110.26(F)(1)(a) there shall be no foreign piping in dedicated electrical space, 110.22 All disconnects shall be identified with sufficient durability to withstand environment
|
ELE06-01823
| Permanent Service | 11/17/2006 | 11/17/2006 | 11/17/2006 2:32:23 PM | P | PASS |
|
|
val; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s exst meter pak n ok
|
ELE06-03376
| Final | 11/16/2006 | 11/17/2006 | 11/17/2006 1:39:59 PM | P | PASS |
|
|
questions pls call Mike @###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer ok to final core and shell, shall id disconnects, no card signed
|
ELE06-03372
| Final | 11/17/2006 | 11/17/2006 | 11/17/2006 12:51:34 PM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/17/2006 at 6:15:56 AM. Contact: ###-####. ok to final
|
ELE06-04217
| Final | 11/17/2006 | 11/17/2006 | 11/17/2006 12:50:38 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/17/2006 at 8:47:21 AM. Contact: ###-####. corr made, signed struct card
|
ELE06-02657
| Electrical Rough-In | 11/17/2006 | 11/17/2006 | 11/17/2006 12:25:45 PM | P | PART |
|
|
Loren Electrical r/i for Temporary Occ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles signed t/o card , need to see counter , entry lights, 422.16(B)!1) max length disposal cord shall be 3'
|
ELE06-03089
| Electrical Rough-In | 11/15/2006 | 11/17/2006 | 11/17/2006 11:23:44 AM | A | PART |
|
|
joe ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to cover cond from house to garage only, need to see gec
|
ELE06-02560
| Electrical Rough-In | 11/16/2006 | 11/17/2006 | 11/17/2006 10:46:04 AM | A | CANC |
|
|
Need a temporary occupancy please. Outdoor canopies need inspected for cover.Call Loren at ###-#### thank you; Phone #: ###-#### Internet Inspection Request from: Loren Ramsey called , wrong job
|
ELE06-04271
| Permanent Service | 11/16/2006 | 11/17/2006 | 11/17/2006 10:35:43 AM | A | PASS |
|
|
randall ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told owner to triangulate guy wires, p/s o/h rec ok
|
ELE06-03809
| Final | 11/16/2006 | 11/17/2006 | 11/17/2006 10:24:06 AM | A | CANC |
|
|
Ceiling inspection; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot wrong type insp, see ri
|
ELE06-03809
| Electrical Rough-In | 11/17/2006 | 11/17/2006 | 11/17/2006 10:23:41 AM | P | PASS |
|
|
Ceiling inspection; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok to cover ceiling, need tiles out to check lv later at power poles
|
ELE06-04015
| Rough-In Permanent Service | 11/16/2006 | 11/17/2006 | 11/17/2006 10:03:14 AM | A | CANC |
|
|
Underground inspection only.; Phone #: ###-#### Internet Inspection Request from: Jeff Durham wrong type inspection, called, u/g for ipco
|
ELE06-04126
| Electrical Rough-In | 11/16/2006 | 11/17/2006 | 11/17/2006 9:57:52 AM | A | PASS |
|
|
any questions please call Jesse Collingsworth; Phone #: ###-#### Internet Inspection Request from: Jeff Radford interior walls only ok to cover
|
ELE06-04019
| Electrical Rough-In | 11/16/2006 | 11/17/2006 | 11/17/2006 9:23:28 AM | A | PASS |
|
|
Rough In Walls; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson walls only ok to cover
|
ELE06-04217
| Final | 11/16/2006 | 11/17/2006 | 11/17/2006 8:38:19 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 11/16/2006 at 11:18:14 AM. Contact: ###-####. met elect, need to see cable supports, finish grid, panel schedules, no violations shall be retained,
|
ELE06-03275
| Electrical Rough-In | 11/17/2006 | 11/17/2006 | 11/17/2006 8:30:58 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/17/2006 at 6:45:07 AM. Contact: ###-####. ceiling main area ok to cover
|
ELE06-04278
| Rough-In Permanent Service | 11/17/2006 | 11/17/2006 | 11/17/2006 5:14:00 AM | A | PASS |
|
|
ric ok, p/s o/h n (rec) ok
|