Inspections for the day of: Tuesday, November 17, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00972 FIRE-Final Inspection11/17/200911/17/200911/17/2009 4:58:13 PMPFAIL
See fire code review notes for details on issues to be addressed including smoke alarms-items #21-24, provide knox box-item #3, post fire extinguishers-item #7, manual thumbturns are not allowed-item #8, provide signage at the fire riser room door-#19, post building address per #6. Discussed project related FIR permits and completion schedule.
FIR09-00476 INSP-Final Inspection11/17/200911/17/200911/17/2009 4:49:35 PMPPART
Items needed for final include head guards at sprinklers in low ceilings, signage at the antifreeze riser, state fire marshal tags, open the valve to the expansion tank, obstructed head at one closet, all valves controlling the water supply to the fire sprinkler system shall be electrically supervised per IFC 2006 sec. 903.4- see fire code review note #10.
FIR09-00391 INSP-Final Inspection11/17/200911/17/200911/17/2009 4:42:21 PMPPASS
Functional site testing completed in conjunction with fire alarm work on the adjacent truck return and dispatch building, inspection passed. Permit final okayed.
BLD09-01337 FIRE-Final Inspection11/17/200911/17/200911/17/2009 2:37:34 PMAPASS
Noted correction items verified for completion, fire life safety final approved.
FIR09-00587 INSP-Final Inspection11/17/200911/17/200911/17/2009 2:36:36 PMAPASS
Fire alarm permit work finaled.
FIR09-00548 INSP-Final Inspection11/16/200911/17/200911/17/2009 2:36:02 PMAPART
Final pending interconnection of the new mag lock at the main entry door to relelase on fire alarm, all valves controlling water supply to the fire sprinkler system shall be electronically supervised-see fire code review note #4, provide signage at the door the FACP room per note #14, need to post a knox box per note #13, revised plans to indicate the addtional tamper switches and mag lock relay.
BLD04-02761 FIRE-Final Inspection11/13/200911/17/200911/17/2009 2:30:19 PMAPASS
Fire life safety site inspection completed acceptable.