Inspections for the day of: Monday, November 17, 2014.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-02234 Final11/17/201411/17/201411/17/2014 4:27:46 PMPFAIL
spoke to contractor
440.52 overload protection to be sized to a/c units accordingly
110.26 working clearance about electrical equipment, a/c disconnects
422.31 Disconnecting means of permanently installed appliances, hood, micro, dishwasher
210.8A5 GFI protection required unfinished basemnet
410.16B. luminaire clothes closet, no open lamp fixtures allowed
362.30B. strap riser within 3 ft. of meter
BCC 4.05.26 all work to be complete for inspection-missing plate in living room cabinet, bedroom light not working
BCC. Energy Code, 50% minimum of fixtures to be of energy efficient type.
ELE13-03193 Final11/17/201411/17/201411/17/2014 4:23:39 PMPDONE
Ryan is contact. Thank you. Phone #: ###-#### Inspection requested via web by Chris Chesnut
Needed home inspected, power pole has been removed from job, placing final inspection to close this permit
ELE11-02161 ELE-Aging Inspection11/17/201411/17/201411/17/2014 2:39:31 PMPDONE
No work performed under this permit. See permit ELE11-02756 for job.
ELE11-02161 Final11/17/201411/17/201411/17/2014 2:38:46 PMPDONE
No work performed under this permit number. See permit ELE11-02756 for job.
ELE14-02512 Final11/17/201411/17/201411/17/2014 2:32:18 PMPCANC
Call prior to going Phone #: 5149748 >> Inspection requested via mobile web by Steve
wanted conference, wrong inspection type
ELE14-02512 Conference11/17/201411/17/201411/17/2014 2:31:44 PMPDONE
Call prior to going Phone #: 5149748 >> Inspection requested via mobile web by Steve
Discuss options to correct for final inspection
ELE14-03187 Permanent Service11/17/201411/17/201411/17/2014 2:04:54 PMPFAIL
PLEASE CALL FOR ACCESS, ###-#### Phone #: ###-#### Inspection requested via web by John VanZandt
250.52 Grounding electrode required, metal water line disconnected
250.53 Supplemental ground required
ELE14-03159 Final11/17/201411/17/201411/17/2014 1:17:31 PMPCANC
Kevin Phone #: ###-####
Still no inspection performed yet for system install. see permit ELE14-03086
ELE14-02367 Final11/17/201411/17/201411/17/2014 1:04:09 PMPFAIL
Phone #: ###-#### Inspection requested via web by David Nelson
still missing extension rings
could not leave a message, voicemail box was full
ELE14-02370 Final11/17/201411/17/201411/17/2014 12:40:57 PMPFAIL
Phone #: ###-#### Inspection requested via web by John VanZandt
210.52E1 Outdoor receptacle required front of home
422.31 Disconnecting means of permanently connected appliances, hood and heaters
400.8 Flexible cords, uses not permitted
1. as a substitute for fixed wiring
5. where concealed
BCC. all work completed for final
ELE11-02187 ELE-Aging Inspection11/17/201411/17/201411/17/2014 10:55:25 AM DONE
Spoke to Deb, will check with service tech again about getting final inspection
ELE14-03085 Electrical Rough-In11/14/201411/17/201411/17/2014 9:13:58 AMAPASS
Wall Inspection - Geoff Hannaford is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce
RI, OK to cover walls and ceiling of locker room area
ELE13-01418 Final11/14/201411/17/201411/17/2014 8:43:15 AMAFAIL
call 15min before//scott Phone #: ###-####
Needs ground connection, outlet to right of refridgferator
Extension rings required in tile backsplash
ELE14-03110 Permanent Service11/12/201411/17/201411/14/2014 11:51:30 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder