ELE14-02234
| Final | 11/17/2014 | 11/17/2014 | 11/17/2014 4:27:46 PM | P | FAIL |
|
|
spoke to contractor 440.52 overload protection to be sized to a/c units accordingly 110.26 working clearance about electrical equipment, a/c disconnects 422.31 Disconnecting means of permanently installed appliances, hood, micro, dishwasher 210.8A5 GFI protection required unfinished basemnet 410.16B. luminaire clothes closet, no open lamp fixtures allowed 362.30B. strap riser within 3 ft. of meter BCC 4.05.26 all work to be complete for inspection-missing plate in living room cabinet, bedroom light not working BCC. Energy Code, 50% minimum of fixtures to be of energy efficient type.
|
ELE13-03193
| Final | 11/17/2014 | 11/17/2014 | 11/17/2014 4:23:39 PM | P | DONE |
|
|
Ryan is contact. Thank you. Phone #: ###-#### Inspection requested via web by Chris Chesnut Needed home inspected, power pole has been removed from job, placing final inspection to close this permit
|
ELE11-02161
| ELE-Aging Inspection | 11/17/2014 | 11/17/2014 | 11/17/2014 2:39:31 PM | P | DONE |
|
|
No work performed under this permit. See permit ELE11-02756 for job.
|
ELE11-02161
| Final | 11/17/2014 | 11/17/2014 | 11/17/2014 2:38:46 PM | P | DONE |
|
|
No work performed under this permit number. See permit ELE11-02756 for job.
|
ELE14-02512
| Final | 11/17/2014 | 11/17/2014 | 11/17/2014 2:32:18 PM | P | CANC |
|
|
Call prior to going Phone #: 5149748 >> Inspection requested via mobile web by Steve wanted conference, wrong inspection type
|
ELE14-02512
| Conference | 11/17/2014 | 11/17/2014 | 11/17/2014 2:31:44 PM | P | DONE |
|
|
Call prior to going Phone #: 5149748 >> Inspection requested via mobile web by Steve Discuss options to correct for final inspection
|
ELE14-03187
| Permanent Service | 11/17/2014 | 11/17/2014 | 11/17/2014 2:04:54 PM | P | FAIL |
|
|
PLEASE CALL FOR ACCESS, ###-#### Phone #: ###-#### Inspection requested via web by John VanZandt 250.52 Grounding electrode required, metal water line disconnected 250.53 Supplemental ground required
|
ELE14-03159
| Final | 11/17/2014 | 11/17/2014 | 11/17/2014 1:17:31 PM | P | CANC |
|
|
Kevin Phone #: ###-#### Still no inspection performed yet for system install. see permit ELE14-03086
|
ELE14-02367
| Final | 11/17/2014 | 11/17/2014 | 11/17/2014 1:04:09 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson still missing extension rings could not leave a message, voicemail box was full
|
ELE14-02370
| Final | 11/17/2014 | 11/17/2014 | 11/17/2014 12:40:57 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by John VanZandt 210.52E1 Outdoor receptacle required front of home 422.31 Disconnecting means of permanently connected appliances, hood and heaters 400.8 Flexible cords, uses not permitted 1. as a substitute for fixed wiring 5. where concealed BCC. all work completed for final
|
ELE11-02187
| ELE-Aging Inspection | 11/17/2014 | 11/17/2014 | 11/17/2014 10:55:25 AM | | DONE |
|
|
Spoke to Deb, will check with service tech again about getting final inspection
|
ELE14-03085
| Electrical Rough-In | 11/14/2014 | 11/17/2014 | 11/17/2014 9:13:58 AM | A | PASS |
|
|
Wall Inspection - Geoff Hannaford is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce RI, OK to cover walls and ceiling of locker room area
|
ELE13-01418
| Final | 11/14/2014 | 11/17/2014 | 11/17/2014 8:43:15 AM | A | FAIL |
|
|
call 15min before//scott Phone #: ###-#### Needs ground connection, outlet to right of refridgferator Extension rings required in tile backsplash
|
ELE14-03110
| Permanent Service | 11/12/2014 | 11/17/2014 | 11/14/2014 11:51:30 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
|