Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF15-00035 INSP-Sprinkler Rough-in11/17/201511/17/201511/17/2015 11:23:16 AMPDONE
Completed. See previous entry note.
NAF15-00035 INSP-Sprinkler Rough-in11/17/201511/17/201511/17/2015 10:16:08 AMADONE
Completed underground supply inspection. Verified depth and thrust blocks. Underground OK to cover.
NAF15-00035 INSP-Sprinkler Rough-in11/17/201511/17/201511/17/2015 8:06:15 AMPDONE
Early Start Inspection on 11/3 for riser stub in. Riser ok to pour floor slab, discussed pouring around a ring for seismic protection. Verified appropriate depth on stub outside of building footing. End of pipe submerged in dirt, unsure if capped, ensure flush is done well at later date.

Initially posted to NAF15-00025 which is alarm permit. Added here to ensure documented appropriately.