FIR03-00450
| FIR-Aging Inspection | 11/18/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | | NR |
|
|
Stopped at the project. Could not get access but by looking through the window I could see that work is still in progress 11/19/2003 10:54:53 AM
|
BLD03-00379
| FIRE-Final Inspection | 11/17/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | A | CANC |
|
|
Tony; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
BLD03-02103
| FIRE-Final Inspection | 11/17/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | A | PART |
|
|
pete; Phone #: ###-#### A temporary occupancy was given with dave millers permission until the emergency light at the main exit is repaired or replaced 11/18/2003 2:49:00 PM
|
FIR03-00671
| INSP-Final Inspection | 11/17/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | A | FAIL |
|
|
sidewall head in office 104 exceeds 7'-0" off of wall 11/18/2003 10:23:26 AM
|
FIR03-00532
| INSP-Final Inspection | 11/17/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | A | PASS |
|
|
Please notify Warner for time of inspection.; Phone #: ###-#### Internet Inspection Request from: Teresa Costello
|
BLD03-02469
| FIRE-Final Inspection | 11/17/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | P | PASS |
|
|
life safety finaled 11/18/2003 12:11:34 PM
|
BLD02-01074
| FIRE-Final Inspection | 11/17/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | P | FAIL |
|
|
Provide "door to remain unlocked..." sticker, provide two 2a10bc fire extinguishers mounted in a normal path of travel at 48" to handle with current inspection tags, provide latch on the half door so it can be opened as one door, remove thumb turns. Provide permits for the tenant improvements 11/18/2003 4:04:06 PM
|
BLD03-02665
| FIRE-Final Inspection | 11/18/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | P | PASS |
|
|
life safety finaled 11/18/2003 12:10:58 PM
|
BLD03-00493
| FIRE-Final Inspection | 11/18/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | P | PASS |
|
|
fire life safety for shell ok 11/18/2003 2:31:50 PM
|
BLD03-01836
| FIRE-Final Inspection | 11/18/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | P | FAIL |
|
|
remove thumbturn from the main exit, provide approved door hardware on the east exit door and test the duct smoke detectors 11/18/2003 2:30:48 PM
|
BLD03-00490
| FIRE-Final Inspection | 11/18/2003 | 11/18/2003 | 11/18/2003 12:00:00 AM | P | PASS |
|
|
fire life safety ok for the shell 11/18/2003 2:33:13 PM
|