Inspections for the day of: Thursday, November 18, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00700 INSP-Sprinkler Rough-in/Hydro11/18/200411/18/200411/18/2004 11:30:27 AMPCANC
Contact: Chris - UG Cover Inspection - Would like around 4 PM this afternoon, please call to confirm; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
FIR04-00501 FIR-Aging Inspection11/18/200411/18/200411/18/2004 12:00:00 AM NR
Per Mike with General Fire the inspection will be called in the first of next week 11/19/2004 8:19:30 AM
BLD03-02970 FIRE-Final Inspection11/17/200411/18/200411/18/2004 12:00:00 AMAFAIL
glenn; Phone #: ###-#### General contractor was not on site. Left message on phone. There is still tenting problems in the attic. 11/18/2004 10:25:49 AM
BLD04-00690 FIRE-Conference11/17/200411/18/200411/18/2004 12:00:00 AMADONE
Spoke to Pete about the fire life safety review notes and requirements. 11/18/2004 10:35:17 AM
FIR04-00236 INSP-Final Inspection11/18/200411/18/200411/18/2004 12:00:00 AMAPASS
Fire sprinkler finaled
FIR04-00479 INSP-Final Inspection11/18/200411/18/200411/18/2004 12:00:00 AMAPASS
Fire alarm finaled
FIR04-00368 INSP-Sprinkler Rough-in11/17/200411/18/200411/18/2004 12:00:00 AMAFAIL
Eric; Phone #: ###-#### Inspection was for corrections and tenting on the fourth floor . Corrections are ok but the tenting needs repaired in many locations. I also did rough-in spection for the club house. Uprights are too far from deck in some locations. Branchline over pool appears to exceed 12" from centerline of peak. Hangers are not to top chord. See approved plans for locations of problems. Still need letter from engineer before cover on fourth floor will be given. 11/18/2004 10:14:41 AM
FIR04-00251 INSP-Conference11/18/200411/18/200411/18/2004 12:00:00 AMPDONE
I spoke with the general contractor about the status of the fire alarm and fire sprinkler permits. He said he means to get the project finished up. Permit has expired on 10/25/2004. This will need to be resolve with bill alexander
FIR04-00143 INSP-Sprinkler Rough-in/Hydro11/18/200411/18/200411/18/2004 12:00:00 AMPCANC
duplicate inspection. Rescheduled for tomorrow 11/18/2004 4:01:02 PM
FIR04-00143 INSP-Final Inspection11/17/200411/18/200411/18/2004 12:00:00 AMPCANC
Linda; Phone #: ###-#### Internet Inspection Request from: Cheryl Baumgartner
BLD04-00827 FIRE-Final Inspection11/18/200411/18/200411/18/2004 12:00:00 AMPPASS
fire life safety finaled 11/18/2004 2:30:04 PM