Inspections for the day of: Friday, November 18, 2005.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03702 Final11/18/200511/18/200511/18/2005 4:54:17 PMPPART
Scheduled by a contractor via Hello! on 11/18/2005 at 10:50:52 AM. Contact: ###-####. signed temp occ card, left correction notice,330.10(A) mc cable shall not be installed where subject to physical damage
ELE05-03701 Final11/18/200511/18/200511/18/2005 4:24:02 PMPPASS
Scheduled by a contractor via Hello! on 11/18/2005 at 10:52:00 AM. Contact: ###-####. ok to final, signed occ card
ELE05-04192 Permanent Service11/17/200511/18/200511/18/2005 4:22:54 PMPPASS
100 amp service upgrade, Jimmy's cell ####-#### Internet Inspection Request from: Andy Rose called contr to change wiring on gfci, p/s o/h exst ok
ELE03-03643 Electrical Rough-In11/18/200511/18/200511/18/2005 4:21:31 PMPPASS
scott -; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie told owner to maintain 1 1/4" for some switches, ric ok
ELE05-04170 Permanent Service11/18/200511/18/200511/18/2005 1:37:15 PMPPASS
roy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g reconnect exst meter, ok
ELE05-04172 Permanent Service11/18/200511/18/200511/18/2005 1:36:32 PMPPASS
roy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g reconnect exst meter ok
ELE05-04171 Permanent Service11/18/200511/18/200511/18/2005 1:35:50 PMPPASS
roy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g reconnect exst mter, ok
ELE05-02374 Final11/17/200511/18/200511/18/2005 11:05:42 AMANR
STEVE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy talked to contr, will call ltr, wanted t/o, too much work on going
ELE05-03107 Final11/17/200511/18/200511/18/2005 10:21:06 AMAPASS
greg; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa finished under owner permit, started and ric under ele05-02941. Original contr pulled off job. ok to final
ELE05-03277 Electrical Rough-In11/17/200511/18/200511/18/2005 10:16:10 AMAPASS
Scheduled by a contractor via Hello! on 11/17/2005 at 1:38:56 PM. Contact: ###-####. ok to cover u/g west end of bldg
ELE05-03104 Final11/15/200511/18/200511/18/2005 9:30:10 AMAPASS
CORRECTIONS MADE PER NOTE, BRAD WILL BE ON-SITE, ###-####. THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
ELE05-03702 Final11/16/200511/18/200511/18/2005 9:04:39 AMANR
Scheduled by a contractor via Hello! on 11/16/2005 at 3:42:55 PM. Contact: ###-####. will call in ltr
ELE05-03701 Final11/16/200511/18/200511/18/2005 9:03:33 AMAPART
Scheduled by a contractor via Hello! on 11/16/2005 at 3:43:54 PM. Contact: ###-####. need to replace fixture
ELE05-03591 Final11/17/200511/18/200511/18/2005 9:02:52 AMAPART
Scheduled by a contractor via Hello! on 11/17/2005 at 4:34:19 PM. Contact: ###-####. met contr, they need to find all labels for owner supplied equip,anchor plug mold in cases, close panels,enhance panel schedules, add gfcis by sinks, close opnings in furniture
ELE05-03357 Final11/18/200511/18/200511/18/2005 12:00:00 AMPCANC
Sean, Please inspect around 12:00; Phone #: ###-#### Internet Inspection Request from: Melyne Davis Melody canc
ELE05-04108 Electrical Rough-In11/18/200511/18/200511/18/2005 12:00:00 AMPPASS
ri walls only ok, elect coming back to do 1 1/4"
ELE05-03773 Final11/18/200511/18/200511/18/2005 12:00:00 AMPPART
too much construction material and tools to allow t/o. looked at recpts, still putting up fixtures.
ELE05-03661 Electrical Rough-In11/18/200511/18/200511/18/2005 12:00:00 AMPPASS
ok to cover rest of ceiling
ELE05-03591 Final11/18/200511/18/200511/18/2005 12:00:00 AMPPART
Need to add gfci by sink in break room, left corr notice,210.62 show room recpts shall be added directly above show windows for each 12' or major fraction thereof