Inspections for the day of: Friday, November 18, 2005.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-00458 FIRE-Final Inspection11/18/200511/18/200511/18/2005 6:04:50 PMPCANC
No time for inspection today, need to final alarm and sprinkler permits prior to life safety approval.
FIR05-00618 INSP-Final Inspection11/18/200511/18/200511/18/2005 6:03:18 PMPCANC
No time for this inspection today.
FIR05-00595 INSP-Final Inspection11/18/200511/18/200511/18/2005 6:01:41 PMPCANC
No time for an inspection, however while on site for a sprinkler inspection noticed two AV's are below the 80" min height AFF.
BLD05-02474 FIRE-Final Inspection11/18/200511/18/200511/18/2005 5:55:27 PMPFAIL
The emergency lights failed to function, need permanent address numbers posted, fire sprinkler c/n needs to be completed.
BLD05-02475 FIRE-Final Inspection11/18/200511/18/200511/18/2005 5:52:20 PMPNR
No life safety inspection until fire sprinkler permit has been issued and approved.
BLD05-02359 FIRE-Final Inspection11/16/200511/18/200511/18/2005 5:49:02 PMAFAIL
One emergency light at the main entry is not functional, need permanent address numbers, remove tape and paper at the sprinkler heads and install escutcheons.
BLD05-02222 FIRE-Final Inspection11/18/200511/18/200511/18/2005 5:43:39 PMPFAIL
Missing one required exit sign, one emergency light at the back restroom is not functional, provide exit discharge lighting, exit sign at the main exit does not illuminate on backup power, provide an additional link on opposite side of the roll up door, provide signage at the roll up door, need permanent address numbers, provide curb painting as discussed, main vestibule is not finished at this time.
FIR05-00689 INSP-Final Inspection11/18/200511/18/200511/18/2005 5:36:31 PMPFAIL
Missing a hanger at one arm over greater than 2' above the drop ceiling area in back, the required min. separation must be provided at the two sprig-ups above the restroom.
FIR05-00704 INSP-Alarm Testing11/18/200511/18/200511/18/2005 5:33:34 PMPPART
Fire alarm work is satisfactory, final pending shell alarm final.
FIR05-00777 INSP-Final Inspection11/18/200511/18/200511/18/2005 3:34:28 PMPPASS
Overhead sprinkler work is acceptable, permit finaled.
FIR05-00777 INSP-Sprinkler Rough-in/Hydro11/18/200511/18/200511/18/2005 3:33:21 PMPDEFR
Duplicate inspection called in.
FIR05-00684 INSP-Alarm Testing11/18/200511/18/200511/18/2005 3:17:02 PMPNR
Not ready for inspection per contractor, will reschedule for next week.
FIR05-00793 INSP-Final Inspection11/18/200511/18/200511/18/2005 2:58:46 PMPPASS
Hood suppression system operated correctly under test conditions.
FIR05-00570 INSP-Sprinkler Rough-in/Hydro11/18/200511/18/200511/18/2005 2:57:43 PMPPART
Overhead fire sprinkler rough-in is okay to cover pending verification of coverage for the dormer at the west roof that is not currrently protected, also will need to verify no obstructions develop after the insulation is installed at the roof.
BLD05-01615 FIRE-Final Inspection11/18/200511/18/200511/18/2005 2:02:12 PMPPASS
Fire life safety is satisfactory.
FIR05-00266 INSP-Sprinkler Rough-in/Hydro11/17/200511/18/200511/18/2005 12:28:52 PMAPART
Overhead hydrostatic test passed inspection.
BLD04-00467 FIRE-Final Inspection11/17/200511/18/200511/18/2005 11:35:45 AMAPASS
Fire life safety is acceptable for the shell permit.
BLD05-02476 FIRE-Final Inspection11/16/200511/18/200511/18/2005 11:05:15 AMANR
Not ready for life safety inspection, the related fire alarm and sprinkler permits must be inspected and approved prior to final. The related sprinkler permit has not been issued at this time.
BLD05-01956 FIRE-Final Inspection11/17/200511/18/200511/18/2005 10:58:34 AMAFAIL
Remove surface bolts and door stopper at back double doors, lower the provided fire ext. to 48" max AFF,one bulb at emergency light is out, provide visual indicator at main entry/exit door, post max occupant sign, no storage allowed in the break room, duct smoke detectors may be required at AHU's.
FIR05-00747 INSP-Final Inspection11/17/200511/18/200511/18/2005 9:49:26 AMAPASS
Fire alarm permit finaled.