Inspections for the day of: Friday, November 18, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00504 INSP-Final Inspection11/18/200511/18/200511/18/2005 4:46:23 PMPPASS
Permit finaled
BLD05-02901 FIRE-Final Inspection11/18/200511/18/200511/18/2005 4:44:40 PMPCANC
No time for inspection today
FIR05-00762 INSP-Final Inspection11/17/200511/18/200511/18/2005 4:44:18 PMACANC
No time for inspection today
BLD05-01119 FIRE-Final Inspection11/17/200511/18/200511/18/2005 4:31:43 PMAFAIL
Provide exit signs and emergency lights as marked on sheet E2.1L, provide approved door hardware on both the interior and exterior keyed/deadbolted doors, provide occupandt load sign, provide braille exit signs per plans, provide the correct remote annunciators and test the duct smoke detectors
FIR05-00601 INSP-Sprinkler Rough-in/Hydro11/18/200511/18/200511/18/2005 4:23:10 PMPPASS
Sprinkler piping is ok to cover. Superintendant witnessed the hydro test and it supposedly passed. Will need to get the test cert. Wrong backflow preventor has been installed and will need verification the one that is installed will work.
FIR05-00597 INSP-Sprinkler Rough-in/Hydro11/17/200511/18/200511/18/2005 4:22:38 PMPPASS
Sprinkler piping is ok to cover. Superintendant witnessed the hydro test and it supposedly passed. Will need to get the test cert. Wrong backflow preventor has been installed and will need verification the one that is installed will work.
FIR05-00599 INSP-Final Inspection11/17/200511/18/200511/18/2005 4:17:40 PMAFAIL
Battery calcs, loss of battery and ac passed. But secondary phone line was not supervised. Test stopped with no other items inspected.
BLD05-01935 FIRE-Final Inspection11/16/200511/18/200511/18/2005 4:09:15 PMAPART
A temporary occupancy was given with Daves permission. Provide listed exit discharge lighting and provide fire alarm permit for the future interconnection of the access controled egress doors and the fire alarm sytem. At this time the door mag are installed just not hooked upl
FIR05-00748 INSP-Sprinkler Rough-in11/17/200511/18/200511/18/2005 2:18:37 PMAPASS
piping is ok to cover
FIR05-00716 INSP-Final Inspection11/18/200511/18/200511/18/2005 1:11:01 PMPFAIL
Insulation still needs to be secured to the deck.