FIR08-00575
| FIR-Aging Inspection | 11/18/2008 | 11/18/2008 | 11/20/2008 10:12:44 AM | | DONE |
|
|
Pending site inspection request
|
FIR08-00751
| INSP-Final Inspection | 11/18/2008 | 11/18/2008 | 11/18/2008 4:37:05 PM | P | DEFR |
|
|
Inspection request intended for 11/21 per conversation with contractor.
|
BLD08-00503
| FIRE-Conference | 11/18/2008 | 11/18/2008 | 11/18/2008 4:31:54 PM | P | DONE |
|
|
Regarding approved door hardware requirements, racking permit, and knox box.
|
FIR08-00730
| INSP-Final Inspection | 11/17/2008 | 11/18/2008 | 11/18/2008 4:27:47 PM | A | PASS |
|
|
Final inspection passed after cd settings at all nine a/v's adjusted while on site, revised smoke detector locations accepted, signals and building address verified, permit finaled.
|
FIR08-00761
| INSP-Sprinkler Rough-in/Hydro | 11/18/2008 | 11/18/2008 | 11/18/2008 4:22:44 PM | P | PART |
|
|
Supply line, branch lines and upright heads okayed for rough-in at the lower office areas.
|
FIR08-00331
| INSP-Supply line flush | 11/18/2008 | 11/18/2008 | 11/18/2008 3:29:12 PM | P | DONE |
|
|
Underground flush completed.KR
|
BLD08-01707
| FIRE-Final Inspection | 11/17/2008 | 11/18/2008 | 11/18/2008 1:49:53 PM | A | PASS |
|
|
Fire life safety completed. KR
|
BLD08-02413
| FIRE-Final Inspection | 11/18/2008 | 11/18/2008 | 11/18/2008 1:45:48 PM | P | PASS |
|
|
C/N finished, inspection passed.
|
FIR08-00649
| INSP-Sprinkler Rough-in/Hydro | 11/17/2008 | 11/18/2008 | 11/18/2008 12:48:01 PM | A | PART |
|
|
Overhead rough-in installation for warehouse systems #1 thru 6 passed inspection, noted riser and pump equipment not yet completed, discussed hydro test and pump acceptance schedule.
|
FIR08-00265
| INSP-Final Inspection | 11/17/2008 | 11/18/2008 | 11/18/2008 10:54:07 AM | P | PASS |
|
|
AM fire alarm notification appliance testing completed acceptable, field modifications noted on as-built plans okayed, corrections per last inspection repaired, permit finaled. NOTE: mag locks at access control doors did not appear to drop out on fire alarm condition per IFC requirements-not included in the scope of this permit work.
|
FIR08-00544
| INSP-Sprinkler Rough-in | 11/18/2008 | 11/18/2008 | 11/18/2008 10:43:56 AM | A | PART |
|
|
Site verified relocated head at an exam room and one additional head installed at the common corridor vestibule per plans.
|
FIR08-00698
| INSP-Final Inspection | 11/17/2008 | 11/18/2008 | 11/18/2008 10:31:35 AM | A | PASS |
|
|
Correction field verified, scope of fire sprinkler work passed inspection, permit finaled.
|
FIR08-00331
| INSP-Supply line flush | 11/17/2008 | 11/18/2008 | 11/18/2008 9:48:37 AM | A | NR |
|
|
Water supply not available at the time of inspection, to be rescheduled as discussed.
|
BLD08-02413
| FIRE-Final Inspection | 11/17/2008 | 11/18/2008 | 11/18/2008 9:46:03 AM | A | FAIL |
|
|
Missing one required fire extinguisher-see permit review conditions for details-to be installed as discused and provided with a current certification tag, also noted missing doors and approved hardware at both restrooms.
|