Inspections for the day of: Tuesday, November 18, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00575 FIR-Aging Inspection11/18/200811/18/200811/20/2008 10:12:44 AM DONE
Pending site inspection request
FIR08-00751 INSP-Final Inspection11/18/200811/18/200811/18/2008 4:37:05 PMPDEFR
Inspection request intended for 11/21 per conversation with contractor.
BLD08-00503 FIRE-Conference11/18/200811/18/200811/18/2008 4:31:54 PMPDONE
Regarding approved door hardware requirements, racking permit, and knox box.
FIR08-00730 INSP-Final Inspection11/17/200811/18/200811/18/2008 4:27:47 PMAPASS
Final inspection passed after cd settings at all nine a/v's adjusted while on site, revised smoke detector locations accepted, signals and building address verified, permit finaled.
FIR08-00761 INSP-Sprinkler Rough-in/Hydro11/18/200811/18/200811/18/2008 4:22:44 PMPPART
Supply line, branch lines and upright heads okayed for rough-in at the lower office areas.
FIR08-00331 INSP-Supply line flush11/18/200811/18/200811/18/2008 3:29:12 PMPDONE
Underground flush completed.KR
BLD08-01707 FIRE-Final Inspection11/17/200811/18/200811/18/2008 1:49:53 PMAPASS
Fire life safety completed. KR
BLD08-02413 FIRE-Final Inspection11/18/200811/18/200811/18/2008 1:45:48 PMPPASS
C/N finished, inspection passed.
FIR08-00649 INSP-Sprinkler Rough-in/Hydro11/17/200811/18/200811/18/2008 12:48:01 PMAPART
Overhead rough-in installation for warehouse systems #1 thru 6 passed inspection, noted riser and pump equipment not yet completed, discussed hydro test and pump acceptance schedule.
FIR08-00265 INSP-Final Inspection11/17/200811/18/200811/18/2008 10:54:07 AMPPASS
AM fire alarm notification appliance testing completed acceptable, field modifications noted on as-built plans okayed, corrections per last inspection repaired, permit finaled. NOTE: mag locks at access control doors did not appear to drop out on fire alarm condition per IFC requirements-not included in the scope of this permit work.
FIR08-00544 INSP-Sprinkler Rough-in11/18/200811/18/200811/18/2008 10:43:56 AMAPART
Site verified relocated head at an exam room and one additional head installed at the common corridor vestibule per plans.
FIR08-00698 INSP-Final Inspection11/17/200811/18/200811/18/2008 10:31:35 AMAPASS
Correction field verified, scope of fire sprinkler work passed inspection, permit finaled.
FIR08-00331 INSP-Supply line flush11/17/200811/18/200811/18/2008 9:48:37 AMANR
Water supply not available at the time of inspection, to be rescheduled as discussed.
BLD08-02413 FIRE-Final Inspection11/17/200811/18/200811/18/2008 9:46:03 AMAFAIL
Missing one required fire extinguisher-see permit review conditions for details-to be installed as discused and provided with a current certification tag, also noted missing doors and approved hardware at both restrooms.