ELE08-03061
| Final | 11/18/2008 | 11/18/2008 | 11/18/2008 4:39:39 PM | P | CANC |
|
|
jeremy Phone #: ###-#### wrong type of inspection
|
ELE08-03061
| Electrical Rough-In | 11/18/2008 | 11/18/2008 | 11/18/2008 4:39:12 PM | P | PASS |
|
|
jeremy Phone #: ###-#### ok cover under ground conduit. conf with jeremy needs to bond with #8 solid cu wire & land it with the other bonding wires, also needs to drill & tape lug to metal fence not with self taping screw.
|
ESC07-00904
| General Inspection | 11/18/2008 | 11/18/2008 | 11/18/2008 4:05:10 PM | P | CANC |
|
|
wrong permit number
|
ELE08-00373
| Electrical Rough-In | 11/18/2008 | 11/18/2008 | 11/18/2008 4:03:48 PM | P | PASS |
|
|
John Phone #: ###-#### ok cover hard lid fire ceiling anop
|
ELE07-02895
| Conference | 11/17/2008 | 11/18/2008 | 11/18/2008 3:45:27 PM | A | DONE |
|
|
phil ###-#### t/w tom hines IPCO sent one year demand for building as for nec220.87(1) four hundred amp service is ok. called phil from tri state & advised him of this. advised him that they had to fix code violations with the service. note no esc permit in project
|
ESC08-00556
| General Inspection | 11/18/2008 | 11/18/2008 | 11/18/2008 3:15:56 PM | P | PASS |
|
|
sign posted they have started landscaping looks fine
|
ELE08-02498
| Final | 11/18/2008 | 11/18/2008 | 11/18/2008 3:14:30 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/18/2008 at 10:22:25 AM. Contact: ###-####. ok final
|
ESC08-00726
| General Inspection | 11/18/2008 | 11/18/2008 | 11/18/2008 12:24:22 PM | P | PASS |
|
|
sign posted site looks fine
|
ELE08-02717
| Final | 11/18/2008 | 11/18/2008 | 11/18/2008 12:23:46 PM | P | PASS |
|
|
contact: Bob Schroder Phone #: ###-#### Internet Inspection Request from: Julie Schroder ok final
|
ESC06-01310
| General Inspection | 11/18/2008 | 11/18/2008 | 11/18/2008 11:38:01 AM | A | PASS |
|
|
sign posted sign looks fine
|
ELE08-02700
| Electrical Rough-In | 11/17/2008 | 11/18/2008 | 11/18/2008 10:17:45 AM | A | PART |
|
|
chad Note: 1st floor hall & master bath floor heat Phone #: ###-#### ok cover floor heat entry & master bathrm only note no esc permit in project
|
ELE08-00828
| Electrical Rough-In | 11/17/2008 | 11/18/2008 | 11/18/2008 10:16:10 AM | A | PASS |
|
|
JASON SLAB Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok cover conduit in slab first floor only
|
ESC08-00292
| Site Final | 11/18/2008 | 11/18/2008 | 11/18/2008 9:26:59 AM | A | PASS |
|
|
ok final site looks fine
|
ELE08-01586
| Final | 11/17/2008 | 11/18/2008 | 11/18/2008 9:26:17 AM | A | PASS |
|
|
gary Phone #: ###-#### ok final note people moved in unable to do complete inspection
|
ELE08-03049
| Temporary Service | 11/17/2008 | 11/18/2008 | 11/18/2008 8:26:51 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham t/s o/h n ok note no esc permit in project
|