Inspections for the day of: Thursday, November 18, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00676 FIR-Aging Inspection11/18/201011/18/201011/19/2010 8:26:56 AM PASS
FIR09-00489 INSP-Final Inspection11/18/201011/18/201011/18/2010 1:35:16 PMPCANC
Had to be cancelled due to Micron plan review and Rich stated that he would not be able to make it today either.
FIR09-00488 INSP-Final Inspection11/18/201011/18/201011/18/2010 1:34:40 PMPCANC
Had to be cancelled due to Micron plan review and Rich stated that he would not be able to make it today either.
BLD10-02700 FIRE-Final Inspection11/17/201011/18/201011/18/2010 1:25:48 PMPPASS
Life safety passed.
FIR10-00547 INSP-Final Inspection11/18/201011/18/201011/18/2010 12:59:41 PMPPASS
Permit finaled
FIR10-00566 INSP-Final Inspection11/18/201011/18/201011/18/2010 10:48:36 AMPPASS
Permit finaled
FIR10-00573 INSP-Sprinkler Rough-in11/17/201011/18/201011/18/2010 10:42:19 AMAFAIL
Resubmitt both plans due to: the floor plans don't match the actual wall layout, the site plan and addresses don't match, sprinkler heads used don't match whats installed. Also the insulation located at the deck is creating obstructions the the upright sprinkler heads. A 1" minimum clearance is required per NFPA 13.
FIR10-00572 INSP-Sprinkler Rough-in11/17/201011/18/201011/18/2010 10:41:39 AMAFAIL
Resubmitt both plans due to: the floor plans don't match the actual wall layout, the site plan and addresses don't match, sprinkler heads used don't match whats installed. Also the insulation located at the deck is creating obstructions the the upright sprinkler heads. A 1" minimum clearance is required per NFPA 13.