ELE12-00900
| ELE-Aging Inspection | 11/18/2014 | 11/18/2014 | 11/18/2014 1:50:08 PM | | DONE |
|
|
Left message with Carrianne in the office.
|
ELE14-00212
| Final | 11/18/2014 | 11/18/2014 | 11/18/2014 1:18:01 PM | P | FAIL |
|
|
moved by Cevyn from AM inspection, per owner availability Spoke to Clay BCC. 4.05.32 Code violattions are not to be retained
406.4.D-where means of ground exists, it shall be used, if not, an approved means of replacement receptacle to be used 210.8 outdoor receptacles to be GFI protected and weather resistant type 110.22 Disconnecting means shall be sufficeint durabililty- permanent label of panel 422.31 permanent disconnecting means of permanent appliances- lockout or disconnect of water heater 110.12 Mechanical execution of work, repair water heater wiring 210.8.A.7. GFI protection within 6 foot of sink
|
ELE14-02367
| Final | 11/17/2014 | 11/18/2014 | 11/18/2014 11:52:55 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson corrections made final ok
|
ELE14-03195
| Electrical Rough-In | 11/17/2014 | 11/18/2014 | 11/18/2014 10:45:39 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Nick Larson'I RI, OK to cover, can in shower
|
ELE14-03121
| Electrical Rough-In | 11/17/2014 | 11/18/2014 | 11/18/2014 10:13:01 AM | A | PASS |
|
|
Kevin Phone #: ###-#### underground conduit OK to cover
|
ELE14-00212
| Final | 11/17/2014 | 11/18/2014 | 11/18/2014 10:12:26 AM | A | CANC |
|
|
Please call Amy 15 minutes ahead to meet ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan called and moved to PM inspection
|
GCE14-00191
| GCE-Rough-In Permanent Service | 11/17/2014 | 11/18/2014 | 11/18/2014 9:32:12 AM | A | PASS |
|
|
Rich ###-#### RI, OK PS,UG, N, OK
|
ELE14-01427
| Final | 11/18/2014 | 11/18/2014 | 11/18/2014 12:00:00 AM | P | CANC |
|
|
Late afternoon please Phone #: ###-#### >> Inspection requested via web by Kevin Burke// kevin called and rescheduled for tomorrow morning
|