Inspections for the day of: Wednesday, November 18, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03007 Final11/18/201511/18/201511/18/2015 2:30:09 PMPPASS
Dan Hommel Phone #: ###-#### Inspection requested via web by Kerri Hamilton final ok
MIS15-00292 ELE-Final11/18/201511/18/201511/18/2015 2:07:30 PMPDONE
as per Chad S-ele, plm & structural work being done w/o permits Knocked on door and no answer. Left correction and do not cover electrical wiring on window.
ELE13-01291 Electrical Rough-In11/18/201511/18/201511/18/2015 1:40:32 PMPPASS
Contact Frank for site work underground. Phone #: ###-#### Inspection requested via web by Tom Betty r/i continue slab on slab ground level conduits ( rock climbing area) ok
ELE13-00983 ELE-Aging Inspection11/18/201511/18/201511/18/2015 11:29:54 AM DONE
talked to Terry and he will scedule final
ELE15-03243 Final11/16/201511/18/201511/18/2015 11:18:13 AMAPASS
Carlos Phone #: ###-#### final ok perm. occupancy ok
ELE15-03562 Final11/17/201511/18/201511/18/2015 11:06:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Jim Williams final ok for new loadcenter and rtu's and rooftop conv. outlets
ELE15-03561 Final11/17/201511/18/201511/18/2015 11:04:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Jim Williams final ok on new loadcenter, 2 rtu's and conv outlets on roof
ELE15-02823 Final11/17/201511/18/201511/18/2015 10:48:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Jim Williams final ok for house panel and branch cicuitry from it, including rooftop ,,exterior lights and receptacles, bathrooms and fire alarm power
ELE15-03563 Final11/17/201511/18/201511/18/2015 10:44:17 AMAPASS
Phone #: ###-#### Inspection requested via web by Jim Williams final ok
ELE15-03560 Final11/17/201511/18/201511/18/2015 10:40:46 AMANR
Phone #: ###-#### Inspection requested via web by Jim Williams bahtrooms and exterior fixtures not trimmed out
ELE15-03238 Final11/18/201511/18/201511/18/2015 9:50:51 AMAFAIL
Please inspect the service sub-panel wiring ; GFCI circuits below those 2 panels. Re-using existing ground rod ; water pipe grounding beyond the existing service location. (Please let me know if I need to feed the 125A breaker from the load side of the 200A breaker inside the Meter Main panel. It was wired internally different than I expected so what you see is not what I originally envisioned.) Phone #: ###-#### Inspection requested via web by nathan palmer NOTES: 4/0 ser ok IF not surrounded by insulation in ceilig. OK to insulate walls only for the short run as per 338.10(4) and 310.15(2). Confirm and expose location of existing grounding electrodes and conductors or add 2 ground rods as per NEC 250.52(5). Install intersystem ground termination bar as per 250.94. Confirm buss rating for 125amp breaker installed in service equipment. Not clear on label on panel door. Install plastic bushings on romex connectors with conductors larger than #4.. Needed p/s today, not final
ELE15-03238 Permanent Service11/18/201511/18/201511/18/2015 9:43:44 AMPPASS
Please inspect the service sub-panel wiring ; GFCI circuits below those 2 panels. Re-using existing ground rod ; water pipe grounding beyond the existing service location. (Please let me know if I need to feed the 125A breaker from the load side of the 200A breaker inside the Meter Main panel. It was wired internally different than I expected so what you see is not what I originally envisioned.) Phone #: ###-#### Inspection requested via web by nathan palmer p/s o/h rec ok
ELE15-03073 Final11/17/201511/18/201511/18/2015 8:25:24 AMAPASS
call steve with questions Phone #: ###-#### Inspection requested via web by Don Lustig final ok