Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01483 Electrical Rough-In11/18/201611/18/201611/18/2016 2:08:43 PMPPASS
We need a partial wall cover for all 3 floors on the north side. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
North rooms on floors 1st and 2nd floor panel walls only ok cover
ELE16-03579 Permanent Service11/17/201611/18/201611/18/2016 2:05:34 PMPPASS
I will be ready late morning. Thanks Phone #: ###-#### Inspection requested via web by Mark Morgan
Service ok to energize,
p/s u/g rec ok 1 meter
ELE16-03344 Final11/18/201611/18/201611/18/2016 1:17:17 PMPPASS
Phone #: ###-#### Inspection requested via web by Stephen Kren
Corrections fixed final ok
ELE16-03777 Final11/18/201611/18/201611/18/2016 12:32:39 PMPFAIL
New service on pole in the back corner of the parking lot off 2nd street right behind green house. Phone #: ###-#### Inspection requested via web by Jay Symonds
110.24 Avaliable fault current calculation required
ELE16-01667 Electrical Rough-In11/17/201611/18/201611/18/2016 11:08:58 AMAPASS
Inspect 3rd floor stair landing in stairwell 1 and 2 call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
stair 1@2 protection of MC ok
ELE16-03344 Final11/18/201611/18/201611/18/2016 8:42:18 AMAFAIL
Any questions please let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren
314.20 Boxes not flush with finished material shall have a listed spark ring
110.7 Laundry room in-op/need lamps installed to verify wiring