BLD16-01929
| FIRE-Final Inspection | 11/18/2016 | 11/18/2016 | 11/18/2016 1:49:57 PM | P | FAIL |
|
|
The life safety can be finaled when the project related fire alarm permit has been addressed.
|
FIR16-00599
| INSP-Final Inspection | 11/17/2016 | 11/18/2016 | 11/18/2016 1:49:20 PM | A | FAIL |
|
|
The induct detectors did not shut down the units immediatley as per the IMC. All other items tested ok.
|
FIR16-00442
| INSP-Final Inspection | 11/17/2016 | 11/18/2016 | 11/18/2016 1:23:30 PM | P | CANC |
|
|
The fire alarm system is not ready for testing the interconnections. To be rescheduled.
Joseph Danes is contact. He will be on site all day. Phone #: ###-#### Inspection requested via web by Connie Danes
|
BLD16-02193
| FIRE-Final Inspection | 11/18/2016 | 11/18/2016 | 11/18/2016 12:57:06 PM | P | PASS |
|
|
Life safety passed. Per contractor the internal pocket door is to be disabled permanantly. Per the plan reviewer the door that separates the two tenants is allowed to be locked.
|
FIR16-00444
| INSP-Sprinkler Rough-in/Hydro | 11/17/2016 | 11/18/2016 | 11/18/2016 11:21:51 AM | A | PASS |
|
|
Overhead hydro test passed
|
FIR16-00442
| INSP-Sprinkler Rough-in/Hydro | 11/17/2016 | 11/18/2016 | 11/18/2016 10:38:33 AM | A | PASS |
|
|
Overhead hydro test passed
|
BLD16-02193
| FIRE-Final Inspection | 11/17/2016 | 11/18/2016 | 11/18/2016 10:37:21 AM | A | FAIL |
|
|
Provide ADA single action hardware on the doors as discussed.
|
FIR16-00668
| INSP-Sprinkler Rough-in | 11/17/2016 | 11/18/2016 | 11/18/2016 10:15:35 AM | A | PASS |
|
|
Underground supply piping is ok for cover
|
FIR16-00667
| INSP-Sprinkler Rough-in | 11/17/2016 | 11/18/2016 | 11/18/2016 10:15:12 AM | A | PASS |
|
|
Underground supply piping is ok for cover.
|
FIR16-00284
| INSP-Sprinkler Rough-in | 11/17/2016 | 11/18/2016 | 11/17/2016 3:33:02 PM | A | CANC |
|
|
Rough to cover on first and second floor North side up to Breezeway Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
FIR16-00710
| INSP-Final Inspection | 11/14/2016 | 11/18/2016 | 11/17/2016 12:37:13 PM | A | PASS |
|
|
Permit finaled
|
NAF16-00032
| INSP-Final | 11/16/2016 | 11/18/2016 | 11/16/2016 1:05:09 PM | A | CANC |
|
|
Phone #: 5015792 >> Inspection requested via mobile web by Dirk Inspection cancelled via mobile web on Wednesday, November 16, 2016.
|