ELE14-02852
| ELE-Aging Inspection | 11/18/2019 | 11/18/2019 | 11/19/2019 9:32:30 AM | | DONE |
|
|
Knocked on door at 930am on 11/19/19 no answer. Left notice in mailbox beside front door. Asked to contact me if corrections were made, and to call for a final inspection. If not, to please call with progress on work done.
|
ELE19-03811
| Final | 11/18/2019 | 11/18/2019 | 11/18/2019 3:15:01 PM | P | PASS |
|
|
Lock code on front door 0720 Phone #: ###-#### Inspection requested via web by shane miller Ok final. Panel labeled, intersystem installed. Water heater junction is blanked off.
|
ELE19-04460
| Permanent Service | 11/18/2019 | 11/18/2019 | 11/18/2019 1:22:12 PM | P | PASS |
|
|
Re-energize service after IP underground relocation Phone #: ###-#### Inspection requested via web by Lars Johnson p/s u/g n ok
|
ELE19-04231
| Permanent Service | 11/18/2019 | 11/18/2019 | 11/18/2019 1:21:40 PM | P | PASS |
|
|
200 amp service upgrade, energize service Phone #: ###-#### Inspection requested via web by Dale Johnson p/s o/h n ok
|
ELE19-04227
| Final | 11/18/2019 | 11/18/2019 | 11/18/2019 12:48:45 PM | P | PASS |
|
|
Please call when on the way ###-#### Phone #: ###-#### Inspection requested via web by Same Electric Ok final.
|
ELE19-04386
| Conference | 11/18/2019 | 11/18/2019 | 11/18/2019 10:33:17 AM | P | DONE |
|
|
###-#### Discussed wire type and disconnecting means for 2 circuits going out to shed.
|
ELE19-04386
| Electrical Rough-In | 11/13/2019 | 11/18/2019 | 11/18/2019 10:25:27 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by William Emmons Changed to a conference.
|
ELE19-04449
| Electrical Rough-In | 11/15/2019 | 11/18/2019 | 11/18/2019 10:17:11 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jake Cutler Ok cover kitchen, living area
|
ELE19-04448
| Electrical Rough-In | 11/15/2019 | 11/18/2019 | 11/18/2019 9:22:35 AM | A | FAIL |
|
|
Contact: Mike Wood Master bathroom heated floor. Electrician: Chris Avery ###-#### Phone #: ###-#### Inspection requested via web by Same Electric As per manu specs. 1. Floor heat cannot be under tub. 2. Minimum 2" away from walls and cabinets, mstr vanity. 3. Minimum 4" away from plumbing flange.
|
ELE19-03446
| Final | 11/12/2019 | 11/18/2019 | 11/18/2019 8:59:03 AM | A | PASS |
|
|
Corbin Metcalf ###-#### or Justin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Ok final.
|
ELE19-04427
| Rough-In Permanent Service | 11/15/2019 | 11/18/2019 | 11/18/2019 8:42:35 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Cevyn Recla Ok cover. Mast not strapped, was waiting for siding. p/s o/h n ok
|
ELE19-03996
| Final | 11/15/2019 | 11/18/2019 | 11/15/2019 2:18:47 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Same Electric Inspection cancelled from web by: Same Electric
|